NOTE!
The currents in given ambient temperatures (in chapter 9.2 Vacon® 100 FLOW -
technical data) are achieved only when the switching frequency is equal to or less
than the factory default.
If your process includes a cyclical load, for example if there are lifts or winches, speak to the
manufacturer to get the dimensioning information.
9.1.3
MAINS VOLTAGE 525-600 V
Table 47: The power ratings of Vacon
®
100 FLOW in mains voltage 525-600 V, 50-60 Hz, 3~
Frame
Drive type
Loadability
Motor shaft
power
Continuous
current I
L
[A]
Input current
I
in
[A]
10% overload
current [A]
Max
continuous
current I
S
2s
600 V
10% overload
40°C [Hp]
MR5
0004
3.9
4.6
4.3
5.4
3.0
0006
6.1
6.8
6.7
7.8
5.0
0009
9.0
9.0
9.9
12.2
7.5
0011
11.0
10.5
12.1
18.0
10.0
MR6
0018
18.0
19.9
19.8
27.0
15.0
0022
22.0
23.3
24.2
36.0
20.0
0027
27.0
27.2
29.7
44.0
25.0
0034
34.0
32.8
37.4
54.0
30.0
MR7
0041
41.0
45.3
45.1
68.0
40.0
0052
52.0
53.8
57.2
82.0
50.0
0062
62.0
62.2
68.2
104.0
60.0
MR8
0080
80.0
90.0
88.0
124.0
75.0
0100
100.0
106.0
110.0
160.0
100.0
0125
125.0
127.0
137.5
200.0
125.0
MR9
0144
144.0
156.0
158.4
250.0
150.0
0208
208.0
212.0
228.8
340.0
200.0
VACON · 136
TECHNICAL DATA, VACON® 100 FLOW
9
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205
Содержание 100 flow
Страница 1: ...vacon 100 vacon 100 flow vacon 100 hvac ac drives installation manual wall mounted drives ...
Страница 2: ......
Страница 4: ...VACON 4 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 78: ...3 Remove the cable cover M4x8 MR8 M4x8 MR9 VACON 78 POWER CABLING 5 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...