11 Connect the stripped cables.
a
)
Connect the phase conductors of the mains
cable and of the motor cable into the correct
terminals. If you use a brake resistor cable,
connect its conductors into the correct
terminals.
b
)
Attach the grounding conductor of each cable
to a grounding terminal with a grounding
clamp for grounding conductor.
c
)
Make sure that the external grounding
conductor is connected to the grounding bar.
See chapter 2.4 Grounding and earth fault
protection.
d
)
See the correct tightening torques in Table 26.
A
B
A. Connection of the cables
B. Make a grounding connection
in MR8
A
A. Make a grounding connection
in MR9
POWER CABLING