9.1.4
MAINS VOLTAGE 525-690 V
Table 48: The power ratings of Vacon
®
100 FLOW in mains voltage 525-690 V, 50-60 Hz, 3~
Frame
Drive type
Loadability
Motor shaft power
Continuous
current I
L
[A]
Input
current I
in
[A]
10%
overload
current [A]
Max
continuous
current I
S
2s
600 V
690 V
10%
overload
40°C [Hp]
10%
overload
40°C [kW]
MR6
0007
7.5
6.8
8.3
11.0
5.0
5.5
0010
10.0
9.0
11.0
15.0
7.5
7.5
0013
13.5
11.6
14.9
20.0
10.0
11.0
0018
18.0
15.2
19.8
27.0
15.0
15.0
0022
22.0
19.8
24.2
36.0
20.0
18.5
0027
27.0
23.1
29.7
44.0
25.0
22.0
0034
34.0
27.0
37.4
54.0
30.0
30.0
MR7
0041
41.0
38.4
45.1
68.0
40.0
37.0
0052
52.0
44.9
57.2
82.0
50.0
45.0
0062
62.0
53.2
68.2
104.0
60.0
55.0
MR8
0080
80.0
72.0
88.0
124.0
75.0
75.0
0100
100.0
89.0
110.0
160.0
100.0
90.0
0125
125.0
104.0
137.5
200.0
125.0
110.0
MR9
0144
144.0
140.0
158.4
250.0
150.0
132.0
0170
170.0
155.0
187.0
288.0
150.0
160.0
0208
208.0
177.0
228.8
340.0
200.0
200.0
9.1.5
OVERLOAD CAPABILITY
The low overload means that if 110% of the continuous current (I
L
) is required for 1 minute
every 10 minutes, the remaining 9 minutes must be approximately 98% of I
L
or less. This is to
make sure that the output current is not more than I
L
during the duty cycle.
TECHNICAL DATA, VACON® 100 FLOW
VACON · 137
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
9
Содержание 100 flow
Страница 1: ...vacon 100 vacon 100 flow vacon 100 hvac ac drives installation manual wall mounted drives ...
Страница 2: ......
Страница 4: ...VACON 4 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 78: ...3 Remove the cable cover M4x8 MR8 M4x8 MR9 VACON 78 POWER CABLING 5 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...