UniPOS
Interactive Fire ControlPanel IFS7002
Instruction Manual
Page
42
Revision 2.05
Of 107
Event character
Event code
Specific information
Fault condition
Fault in mains
supply
exited
Fault Mains Power
reset
Fault condition
Fault in back
up battery supply
Fault Battery
Fault condition
Fault in back
up battery supply
exited
Fault Battery reset
Fault condition
Battery low
due to interruption in mains
supply
Battery Low
Fault condition
Battery low
due to interruption in mains
supply
exited
Battery Low reset
Fault condition
Fault in
auxiliary supply device for
external devices
Fault Auxiliary
Power
Fault condition
Fault in
auxiliary supply device for
external devices
exited
Fault Auxiliary
Power reset
Fault condition
Short circuit in
earthing
Fault in Earthing
Fault condition
Short circuit in
earthing
exited
Fault in Earthing
reset
Fault condition
Fault in Module
0
Fault Module 0
Fault condition
Fault in Module
0
exited
Fault Module 0
reset
Fault condition
Watchdog
reset
Watchdog reset
–
Notes:
1. Exit of fault condition
Detector contaminated,
for optical-smoke detectors, is only possible
through removing and cleaning the fire detector (i.e. fault condition
Removed device
is
registered).
2. Exit of fault conditions
Different Device ID, Different Device Type, Different Device Class
and
Device exchanged
is possible through removing the detector (i.e. fault condition
Removed
device
is registered) or through Fire control panel Set Up (i.e. after event
Manual Set Up
or
Remote Set Up
).
3. Fault
condition
Device exchanged
occurs for two devices minimum.
4. Fault condition
Device isolator activated
occurs for two devices (short circuit in the loop
between two devices) or is combined with fault condition
Short circuit in a fire alarm loop
(short circuit in the loop between the control panel and the first/last device). In case more than
one short circuit is registered in the loop, fault
Device removed
for the devices in the isolated
segment of the loop will also occur.
5. Fault
condition
Device isolator to power loop activated
occurs for two devices (short circuit in
the loop between both devices) or is in combination of fault
Short circuit in power loop
(short
circuit in the loop between the control panel and the first/last device). If more than one shot
circuit in the loop is registered, fault
Device isolator to power loop activated
for the devices in
the isolated segment will also occur.
6. Exit of faults
Fire alarm loop not initialized
and
Number of devices in the fire alarm loop
exceeded
can be done through re-initialization of the fire control panel (i.e. after the event
Reset Panel, Manual Set Up
or
Remote Set Up)
7. Exit of fault
Battery low due to interruption of mains supply
is usually followed by
Reset Panel
8. Event
Watchdog Reset
triggers reset of the fire control panel.