UniPOS
Interactive Fire ControlPanel IFS7002
Instruction Manual
Page
52
Revision 2.05
Of 107
To set the current day of the week (line two) use buttons
and
– they will display the
previous or the next day of the week. Moving from Monday to previous day will set the day to Sunday;
moving from Sunday to next day will set the day to Monday.
The calibration index (line four) can be edited using buttons
and
– respectively
decreasing or increasing the index by a single calibration device until the minimum or maximum value
is reached (–30 / +30). Each positive device accelerates the clock at the rate of 10,7s per month;
each negative device delays the clock at the rate of 5,35s per month. The maximum rate is
е
+5,5min
per month or -2,75min per month.
While changing the values in the bottom left section appears the reminder
Data not saved
.
Changes take effect when you press button
, then the reminder
Data not saved
is cleared.
12.3.4. Function
Set
Mode
The function allows the user to set the mode of operation of the fire control panel (Mode:DAY or
Night Mode). While operating in Night Mode, the control panel ignores Fire condition stage I (Phase 1
of fire condition); i.e. upon activation of automatic fire detector and manual activation of manual call
point, the control panel will always enter Fire condition stage II (Phase 2 of fire condition).
Enter the menu to display the
screen:
The current mode of operation is
displayed in inversive colours – white
letters on black background.
Buttons
and
in the right
panel section allow to alternatively
change the mode of operation.
When the mode is changed, in
the bottom section appears the
reminder
Data not saved
.
Changes take effect when you
press button
, then the
reminder
Data not saved
is cleared.
12.3.5. Function
Check LEDs and Buzzer
The function allows checking the
LEDs and the local sounder. Enter
the function to display the following
screen:
When you press button
which is in the middle of the display,
the check-up operation starts –
control panel’s LEDs illuminate and
the local sounder produces a
continuous sound. The text message
on the display changes:
To stop the
Check push button
.
Mode:DAY
17:43:29
Mon 21 Mar 2005
FIRE CONTROL PANEL IFS7002
UniPOS
Check LEDs and Buzzer
To start the Check
push button
Mode:DAY
17:29:43
Mon 21 Mar 2005
FIRE CONTROL PANEL IFS7002
UniPOS
System functions/Set Mode
Mode:DAY
Mode:NIGHT