UniPOS
Interactive Fire ControlPanel IFS7002
Instruction Manual
Page
36
Revision 2.05
Of 107
When you press button
it displays a screen for the status of the device, which number is in
the field:
−
If you enter 0, the first device will be selected;
−
If you enter a number higher than the actual number of devices, the last device will be
selected.
At the same time button
and the number in the Go to field disappear, i.e. are deactivated.
When you press button
and a number is already entered in the
Go to
field, button
and the field are deactivated.
Information for each device, saved in the fire control panel is displayed in the first three lines on
the panel:
−
Number of the loop where the device is integrated and device address in the loop;
−
Number of the zone where the device is integrated – for fire detectors only;
−
Т
ext message for the device;
−
Device type.
The rest of the panel contains information that is being sent by the device. If no communication
with the device is available, the message
Removed device
appears. Otherwise information specific for
each type device is displayed, including:
−
For automatic fire detectors FD7110 and FD7120:
♦
The temperature measured by the fire detector, in Celsius;
♦
Temperature class of the fire detector;
♦
Status of the detector’s isolator – Off (no response) or On (responded);
♦
LED status – Off (not illuminated/ not flashing) or On (illuminated);
♦
Information for Fire condition – the text message
Fire Alarm
appears only when the
detector responded;
♦
Information for Fault condition – the text message
Fault
is displayed only when the fire
detector responded to a fault condition;
−
For automatic fire detectors FD7130:
♦
The smoke concentration measured by the fire detector, in percentage, against the
response threshold for fire condition;
♦
Detector contamination, in percentage, against the maximum permissible
contamination value;
♦
Status of the detector’s isolator – Off (no response) or On (responded);
♦
LED status – Off (not illuminated/ not flashing) or On (illuminated);
♦
Information for the level of detector contamination– the text message
Contaminated
appears only if the fire detector is contaminated and needs cleaning;
♦
Information for Fire condition – the text message
Fire Alarm
appears only when the
detector responded;
♦
Information for Pre-alarm – the text message
PreAlarm
appears only if the smoke
concentration value is near the response threshold for fire condition;
♦
Information for Fault condition – the text message
Fault
is displayed only when the fire
detector responded to a fault condition;
−
For manual call points FD7150:
♦
Status of the manual call point isolator – Off (no response) or On (responded)
♦
LED status – Off (not illuminated/ not flashing) or On (illuminated);
♦
Information for Fire condition – the text message
Fire Alarm
appears only when the
manual call point responded;
♦
Information for Fault condition – the text message
Fault
is displayed only when the
manual call point responded to a fault condition;
−
For automatic fire detectors FD7160:
♦
The temperature measured by the fire detector, in Celsius;
♦
Temperature class of the fire detector;
♦
The smoke concentration measured by the fire detector, in percentage, against the
response threshold for fire condition;