Add addressable output
The menu allows the user to associate separate addressable outputs to the zone. Enter the menu
to display:
−
If no free addressable outputs, not associated to a zone in accordance with the relevant fire
phase are available – a screen with the message
No unused outputs
appears; the only option
is to exit the menu;
−
If a free addressable output,
not associated to the zone in
accordance with the relevant
fire phase is available – a
screen with the first free
addressable output:
For each addressable output is
displayed:
−
The loop where the output
module is included; the loop
address and the number of
the output in the module, if
more than one – in the top
line;
−
Text message for the device
– in the line beneath.
The selected addressable output
is pointed by arrow – „
>>
”.
Buttons
and
in the right panel section are visualized if more that one free addressable
output is available, and the
Go to
field in the heading and the digit buttons appear if free addressable
outputs in more than one module are available.
When you press a digit button, the
Go to
field is activated; you can enter a random 3-digit numbr
for a device. To edit the number, use button
, press it and the last entered digit will be deleted.
The devices obtain numbers according to the following sequence: from the first device in Loop 1
to the last device in Loop 1; from the first device in Loop 2 to the last device in Loop 2.
When you press button
and a number is entered in the
Go to
field, the first free
addressable output whose number is equal to or higher than the number in the field will be selected:
−
If the number is 0, the first free addressable output will be selected;
−
If the number is higher than the number of the device having the last free addressable output,
the last free addressable output will be selected.
Simultaneously the number in the
Go to
field is deleted; i.e. the field is deactivated.
When you press button
after you entered a number in the
Go to
field, the field will be
deactivated
When you press button
and the
Go to
field is empty, the output will be added to the outputs
associated to the zone. When the last free addressable output is added, a screen with the message
No unused outputs
appears; the only option is to exit the menu. When the 30
th
addressable output is
associated to the zone, a screen with the message
Additional addressable outputs can not be
activated upon Fire Phase
X (X stands for the phase number – 1 or 2); the only option is to exit the
menu.
Mode: DAY
14:38:45
Thu 24 Mar 2005
SetUp Zone 1
Fire Phase 1 Outputs Go to:
Total:
17
>>
Lp1
А
ddr25.1
Point 1.025
0
1
2
3
4
5
6
7
8