13.5.3. Menu
Zone parameters
The menu is provided for zone
parameters set up:
−
Manual call point priority –
when the manual call points
have priority, their response
will trigger Fire condition
phase 2 in the zone; if they
do not have priority, their
response will trigger Fire
condition phase 1 in the
zone; i.e. they will be treated
as automatic fire detectors;
−
Coincidence mode – when
set to this mode, the zone will
enter Fire condition phase 1 if
at least 2 low priority fire
detectors are activated;
−
Time Fire Phase 1 – Phase 2 – the delay time before the control panel proceeds from fire
condition stage I to fire condition stage II in the zone;
−
Inspection time – period of time that, when you press button
, will be added to the
remaining time for transition from Fire condition stage I to Fire condition stage II in a zone.
To edit parameters
Manual call point priority
and
Coincidence Mode
use button
– by
pressing the button you can change the value of the parameter alternatively form
Yes
to
No
and vise
versa.
To edit parameters
Time Fire Phase 1 – Phase 2
and
Inspection time
use the digit buttons. When
you press button
the digit at the left side of the cursor will be deleted. If the values for
Time Fire
Phase 1 – Phase 2
and
Inspection time
are higher than 255, they will be automatically replaced by
255 as soon as the last digit is entered.
Mode: DAY
15:41:44
Thu 24 Mar 2005
SetUp Zone 1
Zone parameters
Manual call point Priority:
Yes
Coincidence
Mode:
No
Time Fire Phase 1 – Phase 2: 120 s
Inspection time: 120 s