11. Test condition
11.1. Description
The Fire control panel enters Test Mode after a fire alarm line has been manually set to
operate in test condition. Test Mode condition is set by a pair of DIP-switches ( pos.4, fig.1 ). Each
line has a pair of switchers, whose position is determined by the operation mode ( fig.2 ) of each
separate line.
The Fire Control Panel
provides option for testing LED and
sound signaling indication.
Pressing and holding the
button
illuminates all lights
and LEDs and activates the buzzer.
11.2. Line in Test condition
When a fire alarm line is in test condition, the following operational changes are in effect:
upon registration of Fire condition in this line the sound indications, light indications,
associated outputs do not operate;
upon registration of Fault in a line the sound indicators, light indicators and the relay output for
fault condition do not operate;
the line is being automatically reset ( the power supply is interrupted for 3 s ) every 64s.
11.2.1
. Setting a line in Test condition
Move the pair of switchers into position (OFF ON) according to Table 3.
In this condition are illuminated:
- the individual indicators of
the line with flashing orange light ;
-the indicator with continuous
yellow light
( if there were no lines
in test condition ).
11.2.2
. To cancel Test Condition of a line
Move the pair of switchers into position (OFF OFF) according to Table 3.
The following lights are switched off:
- Individual yellow line indicators;
- indicator
(if no other lines are set to test condition ).