UniPOS Fire Control Panel FS4000
Instruction manual
Page 11
Revision 11/01.17
of 34
7.3. Using the buttons
Active buttons in Duty mode:
- pressing the button Test Indication and Buzzer
activate indication and sound signaling;
- Using the button
in this mode activates the monitored outputs ( or suppresses them if they
were activated ). The aim is to signal for forced evacuation if necessary.
7.4. Additional option
In FS4000 there is opportunity for configuring line(s) in a definite way so that if signal for Fire
condition, the Fire Control Panel enters directly in Fire condition 2
nd
stage. Configuring is described in
section 10.2 and it is in accordance with Table 3. Setting a line in this mode is performed by manual
operation of placing a pair of switchers in appropriate line positions (ON ON).
8. Fire condition
8.1. Description
The Fire Control Panel enters Fire condition upon double activation of a fire detector in any fire
alarm line, for a period not longer than 60 seconds. After the first activation the control panel resets
the fire alarm line for 3 seconds, and expects second activation in the next 60 sec. If activation occurs
in this period, the Fire Control Panel enters Fire Condition. The Fire Control Panel can enter Fire
condition in one fire alarm line or in a number of fire alarm lines.
To exit Fire condition, press
button at Access level 2.
8.2. LED and sound indication
In this condition are illuminated :
- common indicator
with interrupted red light if Fire condition 1
st
stage and continuous red
light if Fire condition is 2
nd
stage;
- Individual red LINE indicators from all lines of which the Fire Control Panel has indicated Fire
condition;
- If the local buzzer is suppressed by button , the indicator is illuminated with red light ;