UniPOS Fire Control Panel FS4000
Instruction manual
Page 7
Revision 11/01.17
of 34
6.
General information
6.1. Access levels
There are 4 levels of access to the variable indications and control functions of FS4000
6.1.1. Access level 1
All persons who would presumably find out and react to alarm for fault condition or fire condition
have access to level 1. All light indicators are visible here.
6.1.2. Access level 2
For the personnel in charge for the fire protection; they shall be trained and authorized to operate the
fire control panel in the following conditions:
Duty Mode;
Fire condition;
Fault condition;
Disabled component;
Test.
To enter Access level 2
place the key in open condition
The following features are accessible:
exit of fire condition (see pp.12-13);
suppressing the outputs activated upon fire condition;
suppressing the local buzzer;
forced proceeding of the monitored outputs;
connection of fire alarm lines and executive devices;
6.1.3. Access level 3
To enter Access level 3 open the front cover of the control panel and .place the key to open
condition
.
The following features are accessible:
all options from Access level 1 and 2;
replacing a burnt fuse;
setting the overdue outputs
disabling a line;
disabling outputs for fire condition;
Setting a line in test mode;
Setting a line in Duty mode with direct Fire condition 2
nd
stage activation;
Switching on / off communication interface RS485;
Choosing user configuration for the outputs;
Module FD4201 assemblage;
Toggle the mode of the “RST” input application;
6.1.4. Access level 4
Accessible for personnel trained and authorized by the Producer to repair the fire control panel
and to modify the software. Special means are required for access to this level.
6.2. Indications and control
Table 1 gives detailed desription of the indications for each status, table 2 presents the basic
means for control. In Appendix 1 is displayed the front panel of the control panel with indications and
control.
Table 1
Conditions of the fire control panel
Indication
All conditions -
The fire control panel is power supplied
Indicator
Power supply
– continuous
green light