UniPOS Fire Control Panel FS4000
Instruction manual
Page 4
Revision 11/01.17
of 34
FIRE CONDITION
– Fire condition phase entered by the control panel upon activation of
automatic fire detector or manual call point. Common light indication and separate light indication for
each line, local light indicators and local sound signaling indicate the phase.
FIRE CONDITION 1
st
STAGE
– Fire condition phase, is when the Control Panel indicates
activation of automatic fire detector or manual call point. This phase continues until estimated time.
Indication includes light indication and local sound signaling.
FIRE CONDITION 2
nd
STAGE
– Fire condition phase, entered by the Control Panel indicates that
the estimated time of fire condition phase first stage has expired or upon manual call point activation.
Indication includes light indication and local sound signaling.
INTERRUPTED LINE OR MONITORED OUTPUT
– non-system
non-fatal fault condition
due to
current value in a
line
or in a
monitored output
lower than the threshold value.
RELAY OUTPUT
– relay, potential-free, switching outputs that control external executive devices.
SYSTEM FAULT
– fault condition due to a fault in a basic component of the fire control panel (or
the system). The System fault may be
a fatal error
or a
non-fatal error
. The event is indicated by
common light indicators and local sound signaling.
REMOVED FIRE DETECTOR
– non-system
non-fatal fault condition
due to removed fire detector
in a
line
.
FUNCTION ''LOGICAL AND “ OF TWO LINES - function that enables the fire Control panel to
indicate FIRE CONDITION FIRST STAGE when authomatic detectors are activated at the same time
in two lines.
3. Function
Fire control panel FS4000 is designed to operate with conventional automatic fire detectors and
manual call points. The panel has outputs provided for external executive devices.
The unit is produced in four versions:
2 fire alarm lines
- FS4000/2
4 fire alarm lines
- FS4000/4
6 fire alarm lines
- FS4000/6
8 fire alarm lines
- FS4000/8
4. Technical features
4.1.
Fire alarm lines:
Maximum number of fire detectors in a line
- 32
Connecting line
- two-wire
Maximum resistance of a line
- 100
4.2.
Current thresholds for:
0÷6mA
- Fault condition
6
÷16mA
- Duty mode
16
÷80mA
- Fire condition
>80mA
- Short circuit
4.3.
Monitored outputs for fire condition:
-- Number
- 2 pcs
Type - potential, relay with independent control
Electrical characteristics - (19
÷27.5)V/1A