Conditions of the fire control panel
Indication
All conditions
Indicator
Delay of outputs
-
continuous yellow light
Fire condition
Common indicator
Fire condition
–
flashing light or
flashing
red light
Fire condition and Fault condition -
Sound signaling is suppressed
Indicator
Stop/Start Buzzer
- continuous red light
Fire condition-
Outputs for fire condition are disabled
Indicator
Stop/Start Outputs
- continuous red light
Fault condition -
all types of faults
Common indicator
FAULT condition
- flashing yellow light
Fault condition
–
System fault
Indicator
System fault
–
continuous yellow light
Fault condition -
Fault in mains supply
Indicator
Fault in mains supply -
continuous yellow light
Fault condition -
Fault in the backup batteries or in the charger
Indicator
Backup battery fault
-
continuous yellow light
Fault condition-
Fault in internal power supply units, voltage for
supply of lines and/or user voltage 24V
Indicator Fault in internal power
supply unit - continuous yellow light
Fault condition -
Fault in a monitored output
Indicator
FAULT in/Disabled
monitored output
–
flashing yellow light
Fault condition
– Earth FAULT
Leakage to earthed wire or earthed case
Indicator Earth FAULT
–
continuous yellow light
Disabled component -
Disabled line or monitored output
Indicator
Disabled component
-
continuous yellow ligh
Test condition
Indicator Test - continuous yellow
light
Condition of the device for RS485 interface
communication
Indicator for the Condition of the device
for RS485 communication
- red LED for a signal confirmation from
Remote Control Panel FS5200R;
- yellow LED Indicates Fault Condition
in the network or in the transmitting device.
Fire condition / Fault condition
Individual indicators for
Fire condition and Fault
Condition in line “N“-
red light and
continuous
signal from the
local buzzer in
Fire condition;
yellow flashing
light and
interrupted
signal from the
local buzzer in
Fault condition;