UniPOS Fire Control Panel FS4000
Instruction manual
Page 5
Revision 11/01.17
of 34
4.4
.
Relay outputs:
4.4.1. Relay outputs for fire condition
Number
- 2
Type
.
- potential-free, 1 switching , 1 NO
.
with independent control
Electrical characteristics
- 3
А/125V AC, 3A/30V DC
4.4.2. Relay output for fault condition
Number
- 1
Type
- potential-free, switching
Electrical characteristics
-
3А/125V AC, 3A/30V DC
4.5
.
Input for remote
“Reset fires” or “Activate monitored outputs”
(refer p.6.3)
:
Reset fire Input for remote Reset fires operation.
Number
- 1
Type
- none-monitored type
activated on short-circuit (from potential-free contact)
Electrical characteristics
- 5 Vdc on normal open state
- 0 Vdc in activation mode
4.6.
Performance
:
Control over fire alarm lines and monitored outputs for fault conditions (short circuit and
interruption) and automatic reset
Detection of removed fire detector and automatic reset;
Identification of manual call points;
LED indication for alarm state and emergency;
Delay of outputs for fire condition with time period of 1, 2, 3, 4, 5, 6 or 7 minutes after fire
condition is registered;
Option for '' LOGICAL AND '' realization of two fire alarm lines;
Duty Mode condition with direct activation of Fire Condition 2
nd
Stage '' for two fire alarm
lines.
Status Indication of the device for data transmission RS485;
Option for switching on/off interface RS485 communication
Built-in buzzer for fire condition
– one tonal, continuous, can be switched off;
Built-in buzzer for fault condition
– one tonal, discontinuous, can be switched off;
Test mode for fire alarm lines;
Disabling fire alarm lines;
Disabling outputs for fire condition.
Expanding the options by means of extra relay outputs for fire condition for each line and
built-in RS485 for operation in a local network.
Input for remote Reset fires operation or remote activation of the monitored outputs for
Fire Alarm Devices (refer p.6.3);
8 pcs. UniPOS Automatic Fire Detectors (or 4 pcs. With connected RI31 remote
indicators) simultaneously in Fire per zone, before the Short-circuit protection of the line
is triggered. It is because of the self-adaptive current thresholds per zone.
4.7.
Indications of registered events:
Light indication
- LED
Sound
- built-in buzzer