UniPOS Fire Control Panel FS4000
Instruction manual
Page 14
Revision 11/01.17
of 34
The button does not affect nor is its action cancelled by the following events:
When new line enters Fire condition, the local buzzer will be activated;
When new fault condition is registered, the local buzzer will be activated.
Access to the button is allowed at Access level 1, 2, 3.
10. Disabled component mode
10.1. Description
The fire control panel enters Disabled component mode after a component has been manually
disabled
– a fire alarm line or a monitored output. The condition is set through microswitchers for
each line separately, and also for outputs for fire condition
– monitored and relay outputs.
The disabled line is switched off ( the power supply is cut off ) and is not monitored for activated
fire detector and faults. The disabled outputs are switched off (the executive device can not operate)
and the monitored output is not monitored for faults.
10.2. Disable/Enable a line:
Duty mode of lines is determined by
a pair of switchers (pos.4, fig.1).
Each line has a pair of switchers,
whose position is determined by the
operation mode ( fig . 2 )
1 2 3 4 5 6 7 8
On
Off
1 2 3 4 5 6 7 8
On
Off
Line 1 Line 2 Line 3 Line 4 Line 5 Line 6 Line 7 line 8
I
II
Fig. 2
For each individual line the following modes are possible (N - line number)
Table 3
Type of Mode
DIP N
(I)
DIP N
(II)
Duty mode
OFF
OFF
Test
OFF
ON
Disabled line
ON
OFF
Duty mode with direct indication of Fire condition 1
st
stage
ON
ON
10.2.1
To disable a line
Move the pair of switchers of the line in position ON OFF according to table 3.