background image

 

Doc No. FM0713 Issue C Page 24 

 12. LOCK RELEASE 

 

 

Depending on the type of door the most appropriate electric lock release and mounting kit should be selected 

for each installation. 

 

The lock should operate from 12V DC for direct connection to the Entel Ultra door entry or PAC access control 

system, if an AC lock or higher voltage DC lock is used then a separate PSU will be required.  

 

If a PAC or other access control system is being used to release the same door lock then see Section 15 for the 

correct method of interfacing the two systems. 

 

12.01 LOCK TYPES 

 

Depending on the type of lock fitted (i.e. fail safe or fail secure) the door panel can be wired to either remove 

power or apply power to release the lock. 

  

 

 

 

 

 

 

 

12.02 LOCK SUPPRESSION 

 

A reverse bias diode or a Varistor/MOV must be fitted directly across all DC lock terminals to prevent voltage 

transients from the lock coil causing malfunction and possible long term damage to the Entel Ultra and/or 

access control system. 

Please note it is not acceptable to fit the suppression device in the door panel or at any 

other point on the wiring, it must be on the lock terminals.

 

 

 

     0V  

                        DC LOCK ONLY 

 

    LOCK RELAY NC1/NO1 

 

 

Diode Type: 1N4001   or   MOV Type: GNR07D330K 

 

12.03 LOCK CONNECTION 

 

The lock relay common terminal (C1) should be linked to +ve (12V DC) inside the Entel Ultra door panel.  

Connect a magnetic lock +ve terminal to the door panel lock relay normally closed output (NC1)  

Connect an electric ve terminal to the door panel lock relay normally open output (NO1)  

In both cases the lock –ve terminal is connected to the door panel –ve (0V). 

 

12.04 LOCK RELEASE DURATION 

 

The time the door lock remains released from the resident’s phone or the Press to Exit button is independently 

programmable; 

The lock release duration from the resident’s phone can be set from 0 to 30 seconds (default 7 seconds). 

The lock release duration from the Press to Exit button can be set from 1 to 120 seconds (default 10 seconds). 

See Section 17.09 for programming details. 

 

 

 

If a PAC access control system is being installed the PTE time will be set on the PAC.  

The duration the lock remains released by the key fob is also set on the PAC. 

 

 

 

 

 

 

 

 

 

 

Magnetic door locks are fail safe. 

These locks require power to keep the door locked.    

 

Basic electric strikes are normally fail secure. 

These locks require power to allow the door to open.  

 

 

Содержание Entel Ultra

Страница 1: ...roduct improvement and reserves the right to modify the specification of its products If any variation to the details in this document are suspected please contact Tynetec s Technical Support on 01670...

Страница 2: ...es 7 5 Distribution Nodes 10 6 Door Panels 13 7 Camera Panel 16 8 Telephones 17 9 Video Phones 19 10 BT DECT Telephone Interface 21 11 Video Amplifiers Switchers 22 12 Lock Release 24 13 Door Contacts...

Страница 3: ...s this also includes a trade timeclock and a low voltage power supply housed in an IP65 lockable steel enclosure The 8 port distribution nodes are available in IP65 ABS or lockable steel enclosures th...

Страница 4: ...sed for the video connection between the node and phone If existing cabling is being utilised then check sufficient cores are available If a PAC reader is fitted in the door panel then an additional 6...

Страница 5: ...onnected to both Distribution Nodes Telephones connected to both Distribution Nodes 2 MULTIPLE SPEECH PATHS OPTION 1 DIGITAL On multi entrance systems multiple speech paths can be achieved by fitting...

Страница 6: ...Distribution Nodes Ground Floor 3 MULTIPLE SPEECH PATHS OPTION 2 DECK ACCESS To help speed the passage of visitors through large deck access systems the floor level functional panels can be connected...

Страница 7: ...p with the door hinged on the left hand side The door can be swapped to hinge from the right or the back plate can be inverted if the cable entry plate is required on the bottom Always ensure propriet...

Страница 8: ...y The battery is protected by a 20mm 4A quick blow fuse located on the battery protection board 4 07 SYSTEM POWER REQUIREMENTS To ensure the Entel Ultra System Node PSU has sufficient capacity the tot...

Страница 9: ...of 0 5mm cable 10 ohms then the drop would be 5V By using 1 pair of wires the resistance will be halved to 5 ohms therefore the volts drop will be halved to 2 5V Always ensure there is a minimum 10 0...

Страница 10: ...rd has an 8 way DIL switch for setting a unique ID Distribution board ID s are set in Binary see table below DIL SWITCH No 1 2 3 4 5 6 7 8 BINARY CODE 1 2 4 8 16 32 64 128 Distribution board ID s shou...

Страница 11: ...in to switch on off with increasing speed for several minutes Remember to set the correct Board ID and press RESET again when the cleaning cycle is complete 5 06 TELEPHONE SYSTEMS Up to 8 flats can be...

Страница 12: ...nes and ZVT455 video phones This Link may be moved to A if alternative manufacturer s telephones are being used that require a switched 0V for the door open LED 5 11 TELEPHONE DISTRIBUTION BUS WIRING...

Страница 13: ...elephone is turned off a not available tone is sounded When the door lock is released a distinct pulsed tone is sounded to indicate the door is open 6 01 DOOR PANEL RANGE 6 02 PAC READER OPTION All do...

Страница 14: ...x for cable entry this may allow water to enter and damage the electronic components or keypad Cable entry into the backbox should be through the side or rear 20mm knockouts provided IMPORTANT the bac...

Страница 15: ...ti entrance systems set DIL switch 1 ON on one door panel only it doesn t matter which one DIL switch 2 should always be OFF 6 09 VOLUME ADJUSTMENT The door panel loudspeaker and telephone earpiece au...

Страница 16: ...be clarified with the Supervising Officer The backbox should be cut into the brick work or door screen and sealed with suitable mastic to prevent water ingress 7 03 SURFACE FLUSH COWLINGS If it is not...

Страница 17: ...in one of two modes Timed Privacy privacy mode will turn off automatically after a pre set time default 12 hours On Off Privacy privacy mode will remain on until the user turns it off To turn privacy...

Страница 18: ...to 70 seconds default 40 seconds There s an option in programming to extend the conversation time until the end of the lock release period 8 06 TELEPHONE CONNECTIONS Each telephone must be individuall...

Страница 19: ...are set via the Jumper pins on the PCB inside the video phone 9 02 RING TONE VOLUME Move the 3 position slide switch on the top left hand side of the video phone to select low medium or high volume r...

Страница 20: ...l reference and function is listed in the table below Also see the wiring diagram ZV508I ZV516I sheet 1 9 08 PICTURE ADJUSTMENT Use a blunt instrument such as a ball point pen to press the 3 hidden bu...

Страница 21: ...tra Distribution Node Connect the interface unit terminal to the Distribution Node output port terminal Connect the interface unit terminal to the Distribution Node output port terminal Connect the in...

Страница 22: ...ransmission distances up to 1000 metres when used with good quality RG59 coaxial cable Both the 2 4 output models have adjustable gain and high frequency lift controls to fine tune the video signal on...

Страница 23: ...12V relay board to automatically select the video signal from the door panel in use Video from door 1 camera passes through the normally closed contacts onto the video distribution bus Video from doo...

Страница 24: ...her point on the wiring it must be on the lock terminals 0V DC LOCK ONLY LOCK RELAY NC1 NO1 Diode Type 1N4001 or MOV Type GNR07D330K 12 03 LOCK CONNECTION The lock relay common terminal C1 should be l...

Страница 25: ...bove ANTI TAILGATE When the door is opened the lock release time will be reset to help prevent unauthorised visitors entering the building during the same lock release period i e Anti Tailgating The d...

Страница 26: ...cover to avoid accidental operation 14 02 EXTERNAL FIREMAN S SWITCH There are a variety of different types of Fireman s Switches available from many different suppliers the exact make and model will...

Страница 27: ...DOOR PANEL 15 PAC EASIKEY 250 The Entel Ultra door entry system can be interfaced to a PAC Easikey 250 access control system to allow residents to enter the building using an electronic key An Easikey...

Страница 28: ...ller and an Entel Ultra door entry system The Easikey 250 should be programmed for a fail secure lock type Refer to the PAC Easikey 250 user and installation guide for full details 15 03 ALTERNATIVE A...

Страница 29: ...13 Set every other weekday starting Monday MO WE FR 14 Set every other weekday starting Tuesday TU TH SA 15 Set 3 consecutive days starting Monday MO TU WE 16 Set 3 consecutive days starting Thursday...

Страница 30: ...tec GUI Graphical User Interface software This software is supplied on a USB flash memory stick along with the programming lead When installing the software you will need to contact Tynetec s customer...

Страница 31: ...now the Comm Port number the software will find the Comm Port being used and enter it into the box IMPORTANT before proceeding your Laptop needs to be connected to the door panel as described in Secti...

Страница 32: ...you may want click on the yellow Attached Notes and Printer Functions button and record some useful details about the site This button is at the bottom of the green Configuration Data area of the scr...

Страница 33: ...numbers have all been entered for the first distribution node The DIL switch graphic will change to show how the actual DIL switches on distribution board 2 will need to be set Continue filling in th...

Страница 34: ...onal door panels Tynetec P No s ZSD501 to ZSD534 DIAL Step Thru Mode for Dial Functional door panels only Tynetec P No ZSD580 If you set DIAL Step Thru Mode then fill each box with flat numbers in the...

Страница 35: ...ed 33 34 35 36 37 38 39 40 41 42 43 44 Refer to Figure 2 3x5 Matrix and enter the flat numbers engraved on the buttons in the relevant boxes on the programming screen Enter Flat numbers here Set Stand...

Страница 36: ...MMING EXAMPLE 3 EXAMPLE 4 If you have a functional door panel WITH display and you cannot work out which button is which then another option is to temporarily Set Door Panel Type to Digital and click...

Страница 37: ...panel display will show HUNG UP LOCK RELEASE TIME This is the time the door lock will remain released from the resident s telephone The LED indicator on ALL telephones will flash green during the lock...

Страница 38: ...annels 1 to 8 on the 8 channel video switcher set with ID 1 These outputs can be used to select the correct entrance panel camera for the door panel in use Door panels with ID s 9 to 16 will activate...

Страница 39: ...roduces a delay of 10 seconds before the same panel can be used make another call The door panel will display HOLD during this 10 second count down period visitors waiting at other entrances have the...

Страница 40: ...th the programming details for the door panel Remember on multi entrance systems you may have more than one File per site if the door panels are programmed differently PRINT COMMISSIONING SHEETS Click...

Страница 41: ...Press the door panel button to call the first flat number Check the flat number displayed is the same as that engraved on the door panel button The telephone in the flat should ring and the display s...

Страница 42: ...turn the timeclock to AUTO mode If an access code is programmed press the door panel CALL button and the display will show CODE Enter the access code then press the CALL button followed by the 1 butto...

Страница 43: ...n the flat you are calling has been left off the hook TRAN the flat you are calling has their call diverted i e your call is being transferred FLAT LOC BUTTON FAULT the telephone has the lock button s...

Страница 44: ...Page 44 Tynetec a business unit of Legrand Electric Ltd Unit 10 Cowley Road Blyth Riverside Business Park Blyth Northumberland NE24 5TF Tel 01670 352 371 Fax 01670 362 807 Email sales tynetec co uk W...

Отзывы: