F4000 LCD Operator's Manual
Document No: LT0117
Placing Into Operation
Page 9-8
19 April 2002
Issue 2.38
9.4.6 INSTALLATION
CHECKLIST
A)
All detectors listed in Appendix A ......................…………………………….
B)
Number of detectors per circuit not exceeded ............……………………..
C)
Detectors suitable for environment installed in .........……………………….
D)
Detectors and FIP located according to standards ........…………………..
E)
Measure and Record AZC alarm & fault voltages ...........………………….
F)
Open and Short circuit each EOL - fault & alarm as approp?……………..
G)
Zone test all AZC .......................................………………………………….
H)
Switch on/off AC 5 times - No false alarms ..............……………………….
I)
All detectors generate alarm on correct zone ............………………………
J)
All MCPs generate alarm on correct zone .................………………………
K)
All Ancillary Control Zone outputs tested ...............…………………………
L)
MAF test to Fire Control Station ........................…………………………….
M)
All zones labelled according to location / function .....………………………
N)
Australian or New Zealand Mode .........................…………………………..
O)
New Zealand Mode - Display Extender
- Brigade Connections OK .........................................................................
- Silence Alarms OK......................................………………………………..
- Trial Evacuation Operates Bells OK.....................…………………………
- RZDU Silence Alarms and Trial Evacuation .(if applicable) ....................
- External Defect OK.....................................………………………………..
- External Evac Defect OK................................……………………………..
- Lamp Test OK...........................................………………………………….
- LEDs & Ancillary Outputs NORMAL OK.....................…………………….
FIRE OK.......................…………………………………….
DEFECT OK.....................…………………………………