F4000 LCD Operator's Manual
Document No: LT0117
Operating Instructions - Zone Functions
Page 7-18
19 April 2002
Issue 2.38
7.6
ZONE STATUS RECALLS
7.6.1 FUNCTION
Allows an operator to recall the status for a specific zone, or, search for those zones meeting
a specified criteria, e.g. in fault or alarm.
7.6.2 OPERATING SEQUENCE - ZONE STATUS
To recall a specific zone's status, press:
where nnn is the zone number. A networked zone may also be recalled, refer Section 2.5.1
for zone numbering details.
The first line of the LCD will show the zone number and any zone name programmed for that
zone.
Note that there may be a delay between requesting a network zone status and display of the
true status, due to network delays. In this case, F4000 will display default text, ie. just the
network zone number, until the data is received. The display will update with the zone name
and status when it is received.
The second line displays the zone alarm type text for that zone, followed by its status.
The status consists of any of the following:
Prealm
- the zone is in prealarm.
Alarm
- the zone is in alarm.
Operate
- the ACZ is operated.
Fault
- the zone is in fault.
Isolate
- the zone is isolated.
Test
- the zone is currently being tested.
ARst
- the zone is currently being auto reset tested.
Normal
- the zone is none of the above.
The status returned by non-F4000 FIPs may be different.
To view the status of other zones, press:
to view the status of the next zone.
to view the status of the previous zone.