Document No: LT0117
F4000 LCD Operator's Manual
Operating Instructions - Zone Functions
Issue 2.38
19 April 2002
Page 7-5
OPERATING SEQUENCE (NETWORKED ZONE) (CONTINUED)
The LCD will display the network zone with a message saying "Network Command Sent".
After a brief period the message should change to "Network Command Accepted", and the
test will begin. Refer to Section 2.5.6 for a description of these and other possible LCD
display messages.
If an exception occurs at the remote FIP, eg. a test failed, then an exception display may be
received indicating the reason why. Refer to Section 2.5.7 for a description of Exception
Messages.
Notes:
(i)
The effect of the test command is dependant upon the receiving FIP type, eg. how
the zones will be tested, how other zones/FIPs, etc, are affected by the test, and so
forth.
(ii)
If an F4000 receives a test command it will process it as if an operator at that FIP
had initiated the command. If the LCD at that F4000 is at its base display, then the
LCD will indicate that a test is in progress. It will not display the abort prompt that
would normally be displayed for a locally initiated test.
(iii)
If the network zone number entered corresponds to a local zone, the LCD/keypad
test menu continues as if a local zone number had been entered. The network zone
test menu is not used, thus no network messages are displayed.