Designers Manual
Advanced Energy CoolX600 Series
3. Adjust output voltages of the first module to the required voltage.
4. Adjust the voltages of the second module to within the parallel voltage
tolerance of the first module output voltage. See
Table 6
‑
7
.
5. Connect a parallel link to the positive terminals of the two modules.
6. If your application uses remote sensing, connect the sense lines to the load.
a. Connect negative sense lines to the low side of load.
b. Connect positive sense lines to the high side of load.
TTaabbllee 66‑‑77.. Standard and wide-trim module parallel voltage tolerances
M
Moodduullee
PPaarraalllleell VVoollttaaggee TToolleerraannccee ((m
mVV))
CmA
± 10
CmB
± 10
CmC
± 10
CmD
± 20
CmM
± 20
CmN
± 20
CmP
± 20
CmQ
± 40
Special parallel connection links can be fitted to modules to reduce wiring
complexity. These links can be specified and fitted by the installer or added at the
factory.
FFiigguurree 66‑‑1177..
Modules connected in parallel with parallel connection links
All module signals are isolated from the module outputs. When modules are
connected in series or parallel, you can implement any module analog control
function for all the modules by paralleling the appropriate signal pins of each module
and providing a single control signal.
Advanced Energy
®
CoolX
®
600 Modular Power Supply
57010208-00B
Installation, Setup, and Operation
6‑11