Troubleshooting components
BMTK-SVN01D-EN
57
®
Table 11. Tracker main logic board LEDs
LED name
LED
number
Color
Description
HI TX
LED6
Green
Flashes when the main module attempts to communicate with the display
module. The main module attempts to communicate with the display module
even when the display module is not installed. With no display module installed,
the LED flashes every two seconds.
HRT
LED5
Green
Shows the status (heart beat) of the CPU. This LED is on continuously while the
controller boots up. It flashes to show processor activity.
CODE
LED4
Red
Shows the status of the controller operating code. This LED is on continuously
while the controller is booting up and/or whenever the controller needs operat-
ing code.
Note: Code can be downloaded to the Tracker controller with the use of the Tracker PC software
if this LED is on.
PC RX
LED7
Green
Shows that EIA-232 traffic is on the PC port. This LED is normally off. Flashes
when the controller receives data from the PC.
PC TX
LED8
Green
Shows that EIA-232 traffic is on the PC port. This LED is normally off. Flashes
when the controller transmits data to the PC.
BOP
LED3
Red
Flashes when the controller binary output relay is energized and when an
appropriate alarm condition exists.
SERVICE
LED9
Red
Shows that Comm5 service is required. This LED is normally off. LED is on
continuously to show that controller hardware is defective. LED is on
continuously to show that the Service pin button (SW2) was pressed. Flashes to
show that the controller must be rebooted.
COMM
LED2
Yellow
Shows that network traffic is on the Comm5 link. Flashes when the controller
receives data from a Comm5 device.
Left LED
None
Green
Shows that an Ethernet link is detected.
Right LED
None
Green
Shows that there is serial traffic between the Ethernet module and the Tracker
main logic board.
Table 12. Alarm LED
State
Color
Description
Normal
Green
LED is on continuously when the controller is operating normally and has received
no alarms of the appropriate severity.
Alarm
Red
Flashes when the controller receives an alarm of the appropriate severity. To
acknowledge the alarm and turn off the LED, press the Alarm function button
displayed on the user interface home screen.
Содержание Tracker Version 12
Страница 1: ...BMTK SVN01D EN Hardware Installation Tracker Version 12 Building Automation System...
Страница 2: ......
Страница 3: ...Hardware Installation Tracker Version 12 Building Automation System BMTK SVN01D EN February 2004...
Страница 4: ......
Страница 30: ...Chapter 2 Termination module mounting 22 BMTK SVN01D EN...
Страница 48: ...Chapter 3 Termination board wiring 40 BMTK SVN01D EN...
Страница 52: ...Chapter 5 Display module mounting 44 BMTK SVN01D EN Figure 22 Tab and slot alignment...
Страница 53: ...Display module mounting BMTK SVN01D EN 45 Figure 23 Display module engagement...