Wire 24 Vac power
BMTK-SVN01D-EN
25
®
Wire 24 Vac power
After the termination module is mounted in the selected location, wire
24 Vac power to the termination board. Table 5 shows the specifications
for power wiring.
IMPORTANT
The 24 Vac wire conduit may not contain input/output or communica-
tion wires. Failure to comply may cause the Tracker controller to mal-
function due to electrical noise.
1.
Route input wires into the termination module through the conduit
box or any of the conduit access openings designated for input and
communication wiring (Figure 12 on page 19).
2.
Wire the two 24 Vac power input wires and the ground wire to the
controller 24 VAC terminals (Figure 14 on page 24).
Table 5. Power wiring specifications
24 Vac power
terminals
Description
Wire specifications
24 Vac
TB1-1, TB1-2,
Earth ground TB1-3
Power input
24 Vac nominal (19–30 Vac), 50/60 Hz,
1 phase 40 VA minimum, class 2
transformer required
Trane recommends 18 AWG (1.02 mm
2
) wire and
metal conduit.
Low voltage (24 Vac) wire must comply with
National Electrical Code (NEC) and federal, state,
and local electrical codes.
Содержание Tracker Version 12
Страница 1: ...BMTK SVN01D EN Hardware Installation Tracker Version 12 Building Automation System...
Страница 2: ......
Страница 3: ...Hardware Installation Tracker Version 12 Building Automation System BMTK SVN01D EN February 2004...
Страница 4: ......
Страница 30: ...Chapter 2 Termination module mounting 22 BMTK SVN01D EN...
Страница 48: ...Chapter 3 Termination board wiring 40 BMTK SVN01D EN...
Страница 52: ...Chapter 5 Display module mounting 44 BMTK SVN01D EN Figure 22 Tab and slot alignment...
Страница 53: ...Display module mounting BMTK SVN01D EN 45 Figure 23 Display module engagement...
Страница 54: ...Chapter 5 Display module mounting 46 BMTK SVN01D EN...
Страница 70: ...Chapter 7 Troubleshooting 62 BMTK SVN01D EN...
Страница 72: ...Chapter 8 Maintenance 64 BMTK SVN01D EN...
Страница 80: ...Appendix A Installation checklists 72 BMTK SVN01D EN...
Страница 87: ......