BMTK-SVN01D-EN
47
®
Chapter 6
PC workstation wiring
The Tracker controller connects to a PC workstation with a direct
connection cable, an internal modem, or an Ethernet connection.
Verify PC workstation specifications
Verify that the PC conforms to the minimum specifications listed on the
insert in the CD jewel case and that the Tracker PC workstation software
is installed.
Direct connection to PC workstation
To make an EIA-232 direct connection between the controller and a PC
workstation, you need an RJ-12 cable and an adaptor matched to the
serial port connector on the PC workstation (Table 10).
Table 10. Cable and adapter specifications for direct connection
Description
Trane part number
RJ-12 interface cable
3591 4260
9-pin female modular adapter
3591 4262
25-pin female modular adapter
3591 4263
The cable and adapter are not shipped with the Tracker controller and
must be purchased separately.
Содержание Tracker Version 12
Страница 1: ...BMTK SVN01D EN Hardware Installation Tracker Version 12 Building Automation System...
Страница 2: ......
Страница 3: ...Hardware Installation Tracker Version 12 Building Automation System BMTK SVN01D EN February 2004...
Страница 4: ......
Страница 30: ...Chapter 2 Termination module mounting 22 BMTK SVN01D EN...
Страница 48: ...Chapter 3 Termination board wiring 40 BMTK SVN01D EN...
Страница 52: ...Chapter 5 Display module mounting 44 BMTK SVN01D EN Figure 22 Tab and slot alignment...
Страница 53: ...Display module mounting BMTK SVN01D EN 45 Figure 23 Display module engagement...
Страница 54: ...Chapter 5 Display module mounting 46 BMTK SVN01D EN...
Страница 70: ...Chapter 7 Troubleshooting 62 BMTK SVN01D EN...
Страница 72: ...Chapter 8 Maintenance 64 BMTK SVN01D EN...
Страница 80: ...Appendix A Installation checklists 72 BMTK SVN01D EN...
Страница 87: ......