Chapter 3 Termination board wiring
24
BMTK-SVN01D-EN
Figure 14. Tracker field wiring connections
2
4
VAC
THERMIS
TO
R
COMM
ALARM
RELA
Y
PRIORI
TY
SHU
TD
O
W
N
ME
TER
INPU
T
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
24 Vac
Line voltage
Line voltage
Comm5
link
Comm5
link
Comm5 device
Comm5 device
Splice
2
1
3
5
4
4
A
A
B
B
A
A
B
B
Legend
Twisted pair, shielded wire
per Trane specifications
Shield termination
Earth ground
Contact points
Thermistor device per
Trane specifications
Transformer
Termination resistor
Shield ground
=
=
=
=
=
=
=
=
LOAD
Figure note
=
Figure Notes:
1 All customer wiring must be in accordance with national, state, and local electrical codes.
2 Trane recommends a dedicated transformer for 24 Vac power.
3 Alarm relay circuit must not exceed 24 Vac, 1 A.
4 Do not apply voltage to the priority shutdown inputs.
5 Example of Comm5 communication link wiring. See product-specific literature for Comm5 wire connection details.
Содержание Tracker Version 12
Страница 1: ...BMTK SVN01D EN Hardware Installation Tracker Version 12 Building Automation System...
Страница 2: ......
Страница 3: ...Hardware Installation Tracker Version 12 Building Automation System BMTK SVN01D EN February 2004...
Страница 4: ......
Страница 30: ...Chapter 2 Termination module mounting 22 BMTK SVN01D EN...
Страница 48: ...Chapter 3 Termination board wiring 40 BMTK SVN01D EN...
Страница 52: ...Chapter 5 Display module mounting 44 BMTK SVN01D EN Figure 22 Tab and slot alignment...
Страница 53: ...Display module mounting BMTK SVN01D EN 45 Figure 23 Display module engagement...
Страница 54: ...Chapter 5 Display module mounting 46 BMTK SVN01D EN...
Страница 70: ...Chapter 7 Troubleshooting 62 BMTK SVN01D EN...
Страница 72: ...Chapter 8 Maintenance 64 BMTK SVN01D EN...
Страница 80: ...Appendix A Installation checklists 72 BMTK SVN01D EN...
Страница 87: ......