![Trane CCE-Compact Series Скачать руководство пользователя страница 108](http://html1.mh-extra.com/html/trane/cce-compact-series/cce-compact-series_installation-operation-and-maintenance_1149551108.webp)
108/115
V07-19.0
Description
R/W
Unit
Modbus
BACnet
LON
Humidifier – power
R
0,1 %
H140
Humidifier_Req
nvoPerc08
Dehumidification – power request for dehumidification
R
0,1 %
H145
Dehumidification
Air quality control:
CO2 – return air quality setpoint for Eco mode
R/W
ppm
H165
Set_CO2Eco
CO2 – return air quality setpoint for Comfort mode
R/W
ppm
H166
Set_CO2Cmf
nviPpm00
[%]
Minimum fresh air damper position (for air quality control)
R/W
0,1 %
H169
Set_MinFreshAirQCtrl
Maximum fresh air damper position (for air quality control)
R/W
0,1 %
H170
Set_MaxFreshAirQCtrl
Air quality control request value
R
0.1 %
H78
Act_AirQCtrlVal
Humidity control mode
0=Return humidity, 1=Supply humidity, 2=Room humidity
R/W
0..2
H79
Set_HumCtrlMode
Circulation damper dehumidification priority
0=Auto, 1=Fresh air, 2=Return air
R/W
0..2
H81
Set_DmpDehumPrio
Circulation damper actual dehumidification priority
0=Fresh air, 1=Return air
R
0..1
H82
Act_DmpDehumPrio
Other:
Alarm acknowledge (1=Acknowledge, automatic return to 0
after 2s)
W
0..1
H220
Set_AlarmAck
Содержание CCE-Compact Series
Страница 1: ...July 2019 AH SVX007A GB Installation Operation Maintenance CCE Compact Air Handling Unit...
Страница 60: ...60 115 V07 19 0 User manual COMPACT V0 03 April 2018 Hotline 39 335 1334212...
Страница 92: ...92 115 V07 19 0 Data point list COMPACT V0 06 April 2018 Hotline 39 335 1334212...