100/115
V07-19.0
23 Data points AHU
Description
R/W
Unit
Modbus
BACnet
LON
Measured values:
Outdoor- / fresh air temperature
R
0,1 °C
I1
OutDoorTemp
nvoTemp01
Supply air temperature
R
0,1 °C
I2
SupplyTemp
nvoTemp02
Supply air humidity
R
0,1 %
I6
SupplyHumidity
nvoHum00 [%]
Return air temperature
R
0,1 °C
I3
ReturnTemp
nvoTemp03
Return air humidity
R
0,1 %
I7
ReturnHumidity
nvoHum01 [%]
Room temperature
Room unit
R
0,1 °C
I22
RoomTemp
nvoTemp06
Saturation temperature
R
0,1 °C
I4
SaturationTemp
nvoTemp04
Return air quality CO2
R
ppm
I16
ReturnAirQuality
nvoPpm00
Supply airflow rate
R32
m³/h
I17
SupplyFlow
nvoFlow00 [l/s]
Return airflow rate
R32
m³/h
I19
ReturnFlow
nvoFlow01 [l/s]
Supply air duct pressure
R
Pa
I8
SupplyDuctPressure
Return air duct pressure
R
Pa
I9
ReturnDuctPressure
Actual outdoor enthalpy
R
0.1 kJ/kg
I23
Act_OutEnth
Actual supply enthalpy
R
0.1 kJ/kg
I24
Act_SuEnth
Actual return enthalpy
R
0.1 kJ/kg
I25
Act_EhEnth
Actual room enthalpy
R
0.1kJ/kg
I27
Act_RoomEnth
Operating mode: