The 2 safety thermostats are equipped with manual reset.
-
After triggering, the reason for stopping must be detected and eliminated before the reset of the
thermostat!
Thermostat 1 (Figure 70 and Figure 71)
-
Position of thermostat body: fastened on the electric heater at the connection side, is accessible
by removing the electric heater access panel.
-
Triggering temperature: pre-set – value must not be changed.
-
Sensor position: between heating bars.
-
Function: alarm stop in case of over temperature because of low airflow issues
Figure 70:
Thermostat with
cover cap on the reset button
Figure 71:
Thermostat with
uncovered reset button
Thermostat 2 (Figure 72)
-
Position of the thermostat casing: fastened on the outside panel of AHU casing
-
Triggering temperature: set to 70 °C – value must not be changed
-
Sensor position: downstream of the electric heater in upper area of airflow
-
Function: alarm stop in case of over temperature because of missing airflow
Figure 72:
Thermostat 2
Connection box may reach high temperatures. For suitable connection, use heat-resistant cables
(admissible operation temperature min. 110 °C), for example silicone, Teflon or glass fiber insulated
cables.
Cover cap on reset button
Reset button