V07-19.0
95/115
Parameter
Value
Description
Even
Even parity
Odd
Odd parity
Response timeout
Response timeout setting [5 s]
Termination
Enable
termination resistor [Passive]
Passive
No termination
Active
Termination
General
Module configuration/info
Software version
Display software version
Device ID
Display device ID
Module
Display module information
Use default
Active
Set back to the default settings
Table 37:
Modbus RTU configuration
22.2.2
BACnet MS/TP
Parameter
Value
Description
State
Display hardware state of the module
Comm failure
Display communication error
Passive
No communication error
Active
Communication error
BACnet:
Configuration of the BACnet side
Device name
Device name setting [POL904_......]
Device ID
Device ID setting [4194303]
Address
BACnet MS/TP address setting [18]
Imperial unit
system
Use of imperial unit system [No]
No
Metric unit system
Yes
Imperial unit system (inch, °F, …)
Unicode
Enable Unicode [Passive]
Description
language
Description language setting for data point list [English]; do not change it!!
Security level
Security level setting [0]
Alarm server ID
Alarm server ID setting [1]
Alarm device ID1
Alarm device ID1 setting [0]
Alarm device ID2
Alarm device ID2 setting [0]
Comm mapping
Used mapping setting [16384 = COM1]; do not change it!!
Interface:
Configuration of the physical interface