V07-19.0
57/115
Component
Action
Section
month
ly
¼ year
½ year
year
Reference chapter
Housing
Ch / Cl
Housing inside and outside
X
Fan / motor
Ch
Corrosion check
X
Ch
Flexible connection
X
Ch
Protection grid
X
Ch / Cl / M
Motor, general
X
Ch
Check current
consumption
X
Filter
Ch / Cl / M
Panel filters
X
Ch / Cl / M
Bag filters
X
Heat exchanger
Ch / Cl
Fins
X
Ch
Frost protection
X
Ch / Cl
Drain pan
X
Ch / Cl
Droplet eliminator
X
Electric heater
Ch / Cl
E-heater
X
Check e-heater section for thermal damages after mains supply failure!
Dampers
Ch / Cl
Dampers
X
Weather louver
Ch / Cl
Weather louver, grid and hood
X
Energy recovery
Ch / Cl
Plate heat exchanger
X
Ch / Cl
Heat wheel
X
Control cabinet
M
Filter
X
9.1 Electrical connection, control
cabinet
Ch
Fan
X
Ch
Heater
X
Ch
Bolts, electrical connections
X
Table 6:
Maintenance plan
10 Information on airborne noise emitted by the AHUs - on request
Sound data can be printed on request on the technical data sheet, sample see
. The
sound power is specified as A-weighted sound power level:
-
Line 1:
Sound power over the casing
-
Line 2:
Sound power inlet
-
Line 3:
Sound power outlet
The sound through the openings (sound power level in line 2 and 3) is the basis for the calculation
of the on-site sound emissions from the environment.
Figure 78:
Sound data information