84/115
V07-19.0
Alarm class
Description
Alarm(A)
Serious alarm with priority A (high)
Warning(B)
Warning message with priority B (low)
Maintain(C)
Maintenance message with priority C; e.g. dirty filter
Table 28:
Alarm classes
Alarms and warnings are provided as a potential-free contact via the signal module. Alarms of alarm
class
Danger
and
Alarm(A)
are reported at the alarm contact, alarms of the alarm class
Warning(B)
and
Maintain(C)
are reported as a warning.
18 Password handling
The login and logout as well as the change of passwords are performed via the password handling.
The lines
Log in
,
Log out
, and
Change user password
appear only after the login with the user pass-
word
1000
(level 6) or
1001
(level 5); without login, the password entry appears immediately.
The setting of values is only possible after login. The login is indicated by a key symbol in the top
left corner. A login is possible from any menu by long pressing the
Ok
-button.
Passworf handling 1/3
Log in
Log out
Change user password
Figure 102:
Passord handling
Attention: If the changed password is forgotten, then this only can be reset by the service engineer!
Setting
Description
Default
Log in
Login to higher access level, e.g. level 5
Log out
Logout, the display shows the main / start page
Change user password
Change user password for access level 6
The password for access level 5 is greater by 1
and cannot be changed
Table 29:
Password handling
19 Language selection
The language selection is possible without login. English, Italian, German and French can be se-
lected. The selected language does not change even after a power failure.