Description
R/W
Unit
Modbus
BACnet
LON
Current heating setpoint
R
0,1 °C
H61
CtrlHeatSet_act
Current cooling setpoint
R
0,1 °C
H62
CtrlCoolSet_act
Current heating setpoint for saturation temperature (HR,
heating 1, cooling 1)
R
0,1 °C
H63
CtrlSatHeatSet_act
Current cooling setpoint for saturation temperature (HR,
heating 1, cooling 1)
R
0,1 °C
H64
CtrlSatCoolSet_act
Minimal temperature difference cascade control
R/W
0,1 °C
H8
Setpoint_DiffMin
Maximal temperature difference cascade control
R/W
0,1 °C
H9
Setpoint_DiffMax
Recirculation damper – Minimum fresh air damper position
(always valid)
R/W
0,1 %
H71
Set_CircDmpMinFreshAir
Recirculation damper – Maximum fresh air damper position
control (always valid)
R/W
0,1 %
H72
Set_CircDmpMaxFreshAir
Recirculation damper (0=closed, 1=open)
R
0..1
H38
CircDmp_DO
Heating/Cooling battery actual request value
R
0.1 %
H76
H/CBatt_ActReq
Heating/Cooling battery actual mode
0=Winter, 1=Summer
R
0..1
H74
H/CBatt_ActMode
Heating battery 2/post heating battery – valve position
R
0,1 %
H75
HeatBatt2_Valve
nvoPerc03
Heating battery 2/post heating battery – Auto start
temperature
R/W
0.1 °C
H77
HBatt2_PumpAutoSrtTemp
Heating battery 2/post heating battery – Preheating active
R
0..1
H73
HBatt2_PreheatAct
Heating battery 1/pre heating battery – valve position
R
0,1 %
H80
HeatBatt1_Valve
nvoPerc04
Heating battery 1/pre heating battery – pre heating active
R
0..1
H44
HeatBatt1_PreHeatAct
Heating battery 1/pre heating battery – Auto start
temperature
R/W
0.1 °C
H39
HBatt1_PumpAutoStrtTemp
Electric heating battery – power request
R
0,1 %
H85
EBatt_Req
nvoPerc05