94/115
V07-19.0
22.2.1
Modbus RTU
This module provides two communication ports (channel 0, channel 1), in which only channel 0 can
be used for communication to the superior system. Channel 1 is reserved for internal applications.
Parameter
Value
Description
State
Display hardware state of the module
Comm failure
Display communication error
Passive
No communication error
Active
Communication error
Channel 0:
Configuration of channel 0
Slave
Display communication state with the superior system
Passive
No communication
Active
Communication
Slave address
Slave address setting [1]
Baud rate
Baud rate setting [9600]; 1200, 2400, 4800, 9600, 19200 Baud
Stop bits
Number of stop bits [Two]
One
1 stop bit
Two
2 stop bits
Parity
Parity setting [None]
None
No parity
Even
Even parity
Odd
Odd parity
Response timeout
Response timeout setting [5 s]
Termination
Enable
termination resistor [Passive]
Passive
No termination
Active
Termination
Channel 1:
Configuration of channel 1
Enable
Enable communication for channel 1 [Passive]
Slave
Display communication state with the superior system
Passive
No communication
Active
Communication
Slave address
Slave address setting [2]
Baud rate
Baud rate setting [9600]; 1200, 2400, 4800, 9600, 19200 Baud
Stop bits
Number of stop bits [Two]
One
1 stop bit
Two
2 stop bits
Parity
Parity setting [None]
None
No parity