104/115
V07-19.0
Description
R/W
Unit
Modbus
BACnet
LON
Fan control with duct pressure control:
Supply duct pressure for Eco mode
(3)
R/W
Pa
H10
Set_SupplyPressEco
nviPress_Flow00
Supply duct pressure for Comfort mode
(3)
R/W
Pa
H12
Set_SupplyPressCmf
nviPress_Flow01
Supply duct pressure for Night Setback mode
(3)
R/W
Pa
H18
Set_SupplyPressNht
nviPress_Flow04
Return air duct pressure for Eco mode
(3)
R/W
Pa
H14
Set_ReturnPressEco
nviPress_Flow02
Return duct pressure for Comfort mode
(3)
R/W
Pa
H16
Set_ReturnPressCmf
nviPress_Flow03
Return duct pressure for Night Setback mode
(3)
R/W
Pa
H20
Set_ReturnPressNht
nviPress_Flow05
Maximum duct pressure from air quality control
(3)
R/W
Pa
H22
Set_SupplyPressQAirMax
Maximum return duct pressure from air quality control
(3)
R/W
Pa
H24
Set_ReturnPressQAirMax
Maximum supply duct pressure from dehumidification
(3)
R/W
Pa
H30
Set_SupplyPressDeHumMax
Maximum return duct pressure from dehumidification
(3)
R/W
Pa
H32
Set_ReturnPressDeHumMax
Supply duct pressure – request from air quality control
(3)
R
Pa
H97
SupplyPressQAir
Return duct pressure – request from air quality control
(3)
R
Pa
H108
RetunPressQAir
Supply duct pressure – request from dehumidification
(3)
R
Pa
H99
SupplyPressDeHum
Return duct pressure – request from dehumidification
(3)
R
Pa
H96
RetunPressDeHum
Supply duct pressure – current setpoint
(3)
R
Pa
H26
SupplyPressSet
Return duct pressure – current setpoint
(3)
R
Pa
H28
ReturnPressSet
Temperature control:
Temperature control mode
0=Return air/supply air cascade, 1=Constant supply air,
2=Return air, 3=Room/supply air cascade, 4=Room
R/W
0..4
H40
Set_TempCtrlMode
Содержание CCE-Compact Series
Страница 1: ...July 2019 AH SVX007A GB Installation Operation Maintenance CCE Compact Air Handling Unit...
Страница 60: ...60 115 V07 19 0 User manual COMPACT V0 03 April 2018 Hotline 39 335 1334212...
Страница 92: ...92 115 V07 19 0 Data point list COMPACT V0 06 April 2018 Hotline 39 335 1334212...