Object directory
TR-Electronic GmbH 2016, All Rights Reserved
Printed in the Federal Republic of Germany
Page 98 of 153
TR-EMO-BA-GB-0022 v03
09/29/2020
9.4.13 Object 0x6064: Actual Position
Object code
VAR
Data type
INTEGER32
Attribute
ro
Default
0
Min
-
Max
-
PDO mapping
yes
Description
This object displays the actual position value.
9.4.14 Object 0x6065: Following Error Window
Object code
VAR
Data type
UNSIGNED32
Attribute
rw
Default
2
32
-1 (tracking error monitoring switched off)
Min
0
Max
2
32
-1
PDO mapping
yes
Description
This object defines the interval for permissible actual position values around the
nominal position value (0x6062). If the actual position value is outside this interval,
a tracking error exists.
A parameter value of 2
32
-1 deactivates the tracking error monitoring.
A tracking error can occur
if the drive is blocked
if the target speed cannot be reached
if the control parameters are set unfavorably
if the acceleration is to high
9.4.15 Object 0x6066: Following Error Timeout
Object code
VAR
Data type
UNSIGNED16
Attribute
rw
Default
100
Min
0
Max
2
16
-1
PDO mapping
yes
Description
The parameter value specifies the minimum time in 1 ms steps for which a
tracking error must be present before it is displayed as such in the status word.