By clearing the control word bit 2
0
and disabling the operation. The drive goes to
the DS402 state "Switched on", stops and switches off the motor. The stop method
is selected by the option code 0x605C:
0 -> Immediately turn off the drive
1 -> Slow down at the "Profile Deceleration" 0x6084 before turning off the drive.
0xC001 -> Slow down at the "Homing Acceleration" 0x609A before turning off the
drive.
2 or any other value -> Slow down at the "quick stop Deceleration" 0x6085 before
turning off the drive.
By setting the control word bit 2
8
and triggering a stop.
The stop method is selected by the option code 0x605D:
1 -> Slow down at the "Profile Deceleration" 0x6084.
0xC001 -> Slow down at the "Homing Acceleration" 0x609A.
2 or any other value -> Slow down at the "Quick stop Deceleration" 0x6085.
By the digital inputs 2
0
or 2
1
, that are connected to the hardware limit switches by
wires or by SDOs or RPDOs, which are sent by the master. If the drive shall move
away from the allowed range, is stops or stays stopped.
Refer to the description below.
By the target value 0 in the velocity modes, or
by a position ramp in the profile position mode.
All acceleration values are clipped by the "Maximum Acceleration" 0x60C5.
All deceleration values are clipped by the "Maximum Deceleration" 0x60C6.
To detect a stop condition by bit 8 of the control word, read back the control word
0x6040.
To detect a stop condition by the digital input 2
0
and 2
1
, read back the object 0x60FD.
All other stop conditions can be detected by reading the status word 0x6041.
All stop conditions are mutually exclusive, except the digital inputs 2
0
and 2
1
, that may
happen at the same time as any other stop condition. In this case the drive compares
the assigned decelerations and uses the highest value for the stop ramp. Thus it gets
the highest priority.
10.6.3 Control of the Digital Inputs
By setting the digital input bits in the XOR-Mask 0x2F04:02 the polarity of the digital
inputs can be reversed.
By clearing the digital input bits in the AND-Mask 0x2F04:01 the digital inputs can be
blocked for testing, or for using digital inputs, that are transferred remotely from the
master.
Since the software version "V1.1 20-September-2016" both masks are mappable, so
that they can be written not only by SDOs, but also by RPDOs.