CANopen communication
Printed in the Federal Republic of Germany
©
TR-Electronic GmbH 2007, All Rights Reserved
05/16/2007
TR - EMO - BA - DGB - 0013 - 00
Page 225 of 260
4.2.4.6.10 Object 0x605E: Fault behavior
(Fault Reaction Option Code)
Object code
VAR
Data type
INTEGER16
Attribute
rw
Default
2
Min
-32768
Max
32767
PDO mapping
-
Description
This parameter is used to define the reaction of the drive in the event of a fault.
The following values are supported by the encoTRive:
Table 29: Values for Fault Reaction Option Code
Value Meaning
0
Switches drive off.
1
Decelerates drive to a stop with current deceleration.
2
Decelerates drive with deceleration for quick stop (0x6085).
3
Decelerates drive at current limit.
4
Decelerates drive at voltage limit.
4.2.4.6.11 Object 0x6060: Operating mode
Object code
VAR
Data type
INTEGER8
Attribute
wo
Default
0
Min
-128
Max
127
PDO mapping
yes
Description
This parameter is used to define the current operating mode.
The following values are supported by the encoTRive:
Table 30: Values for operating mode
Value Meaning
0
No operating mode defined
1 Positioning
ramp
3 Speed
ramp