GX9 ASD Quick Start Guide
*POFF
*Control Power Under-
Voltage
Under-voltage condition at the 5,
15, or the 24 VDC supply.
• Defective
Control Board
.
• Excessive load on power supply.
• Low input voltage.
Rtry
Retry
After a trip has occurred, for a
number of user-set times an
automatic system restart is
attempted for a qualified trip.
• The
Retry
function is active.
UC
Low-Current Operation
With the
Low-Current Trip
(
F610
) parameter enabled, the
output current of the ASD is
below the level defined at
F611
and remains there for a time
longer than the setting of
F612
.
• Output current too low.
NOFL
Virtual Linear Pump
No Flow
A Low suction/No-flow cut off
condition has been active for a
duration longer than the setting
of
F936
.
• Pump prime required.
• Feed water loss.
• Output valve is closed.
• System may be set to Trip or Alarm for this
condition at
F935
.
*
Reset ignored if active.
LED
Screen
LCD
Screen
Description
Possible Causes/
Troubleshooting
Содержание GX9 ASD
Страница 1: ...GX9 ASD Quick Start Guide TOSHIBA GX9 ASD Quick Start Guide DN 66900 001 March 2014 ...
Страница 2: ......
Страница 3: ...Document Number 66900 001 March 2014 GX9 ASD Quick Start Guide ...
Страница 4: ......
Страница 88: ...78 GX9 ASD Quick Start Guide Figure 33 GX9 ASD 5 0 20 HP Enclosure ...
Страница 89: ...GX9 ASD Quick Start Guide 79 Figure 34 GX9 ASD 25 75 HP Enclosure ...
Страница 90: ...80 GX9 ASD Quick Start Guide Figure 35 GX9 ASD 100 200 HP Enclosure ...
Страница 91: ...GX9 ASD Quick Start Guide 81 Figure 36 GX9 ASD 250 400 HP Enclosure ...
Страница 92: ...82 GX9 ASD Quick Start Guide Figure 37 GX9 ASD 500 800 HP Enclosure ...
Страница 93: ...GX9 ASD Quick Start Guide 83 Figure 38 GX9 ASD 900 1200 HP Enclosure ...
Страница 99: ......