18
GX9 ASD Quick Start Guide
RR
— The default function assigned to this terminal is
Frequency Mode 1
. The
RR
terminal accepts
an analog 0 – 10 VDC input signal that is used to control the function assigned to this terminal. This
input terminal may be programmed to control the speed or torque of the motor via an amplitude setting
or regulate by setting a limit. The gain and bias of this terminal may be adjusted for application-specific
suitability (see
F210
–
F215
).
RX
— The default function assigned to this terminal is
Torque Command
. The
RX
terminal accepts an
analog ±10 VDC input signal that is used to control the function assigned to this terminal. This input
terminal may be programmed to control the speed or torque of the motor via an amplitude setting or
regulate by setting a limit. The gain and bias of this terminal may be adjusted for application-specific
suitability (see
F216
–
F221
).
II
— The
II
terminal is an isolated current input that is used to control the speed or torque of the
motor. Return at
II
(-). Select
VI/II
at
F004
for speed control or select
VI/II
at
F420
for torque
control. The
II
terminal receives a 0 – 20 mA input signal that controls the output 0.0 –
Maximum
Frequency
output or the -250% – 250% torque output of the ASD. Terminal scaling is accomplished
via
F201
–
F206
. The gain and bias of this terminal may be adjusted for application-specific
suitability (see
F470
and
F471
).
VI
— The
VI
terminal is an isolated voltage input that is used to control the speed or torque of the
motor. Select
VI/II
at
F004
for speed control or select
VI/II
at
F420
for torque control. The
VI
terminal receives a 0 – 10 VDC input signal that controls the output 0.0 –
Maximum Frequency
output or the -250% – 250% torque output of the ASD. Terminal scaling is accomplished via
F201
–
F206
. The gain and bias of this terminal may be adjusted for application-specific suitability (see
F470
and
F471
).
Note:
The
VI
terminal or the
II
terminal may be used to control the speed or torque of the
motor. Selecting VI/II at parameter
F004
enables both terminals for use, but both
cannot be used simultaneously. The user connects the proper input (current or
voltage) to the appropriate terminal to be used for control.
P24
— +24 VDC at 200 mA power supply for customer use.
PP
— The function of output
PP
is to provide a 10 VDC/10 mADC (max.) output that may be divided
using a potentiometer. The tapped voltage is applied to the
RR
input to provide manual control of the
RR
programmed function.
OUT1
— The default function assigned to this terminal is
External Device 1
. The function as
External
Device 1
is to activate/deactivate an auxiliary motor once the
Virtual Linear Pump
level has remained
above the
Maximum
threshold
setting
or below the
Minimum
threshold
setting
for the time setting of
F931
. The
OUT1
terminal is rated at 2 A/120 VAC and 2 A/30 VDC and may be set to any of the
functions listed in the
GX9 ASD Installation & Operation Manual
(see
F130
).
OUT2
— The default function assigned to this terminal is
External Device 2
. The function as
External
Device 2
is to activate/deactivate an auxiliary motor once the control level of the
Virtual Linear Pump
settings has remained above the
Maximum
threshold or below the
Minimum
threshold
settings
for the
time setting of
F931
. The
OUT2
terminal is rated at 2 A/120 VAC and 2 A/30 VDC and may be set to
any of the functions listed in the
GX9 ASD Installation & Operation Manual
(see
F131
).
FP
— The default function of this output terminal is to output a series of pulses at a rate that is a
function of the ASD output frequency (50 mA max. at 1.0 kHz to 43.3 kHz). As the output frequency of
the ASD goes up, so does the
FP
output pulse rate. This terminal may be programmed to provide an
output pulse rate that is proportional to the magnitude of the user-selected item listed in the
GX9 ASD
Installation & Operation Manual
. For further information on this terminal, see parameter
F676
.
Содержание GX9 ASD
Страница 1: ...GX9 ASD Quick Start Guide TOSHIBA GX9 ASD Quick Start Guide DN 66900 001 March 2014 ...
Страница 2: ......
Страница 3: ...Document Number 66900 001 March 2014 GX9 ASD Quick Start Guide ...
Страница 4: ......
Страница 88: ...78 GX9 ASD Quick Start Guide Figure 33 GX9 ASD 5 0 20 HP Enclosure ...
Страница 89: ...GX9 ASD Quick Start Guide 79 Figure 34 GX9 ASD 25 75 HP Enclosure ...
Страница 90: ...80 GX9 ASD Quick Start Guide Figure 35 GX9 ASD 100 200 HP Enclosure ...
Страница 91: ...GX9 ASD Quick Start Guide 81 Figure 36 GX9 ASD 250 400 HP Enclosure ...
Страница 92: ...82 GX9 ASD Quick Start Guide Figure 37 GX9 ASD 500 800 HP Enclosure ...
Страница 93: ...GX9 ASD Quick Start Guide 83 Figure 38 GX9 ASD 900 1200 HP Enclosure ...
Страница 99: ......