6
GX9 ASD Quick Start Guide
Protection
•
Ensure that primary protection exists for the input wiring to the equipment. This protection must be
able to interrupt the available fault current from the power line. The equipment may or may not be
equipped with an input disconnect (option).
•
All cable entry openings must be sealed to reduce the risk of entry by vermin and to allow for
maximum cooling efficiency.
•
External dynamic braking resistors must be thermally protected.
•
If the ASD is supplied with a motor as a package, it then becomes a machine and has to meet the
Essential Health and Safety Requirements of the EU Machinery Directive, 2006/42/EC. It is also a
requirement that the system have an
Emergency Off
function that meets the requirements of EN
ISO 13850:2008, and that any local or regional requirements must be met.
•
It is the responsibility of the ASD installer/maintenance personnel to set up the
Emergency Off
braking system of the ASD. The function of the
Emergency Off
braking function is to remove
output power from the ASD in the event of an emergency. A supplemental braking system may also
be engaged in the event of an emergency.
For further information on braking systems, see
parameters
F250
and
F304
.
Note:
A supplemental emergency stopping system should be used with the ASD. Emergency
stopping should not be a task of the ASD alone.
•
Follow all warnings and precautions and do not exceed equipment ratings.
Dynamic Braking Resistor Requirements
When using a
Dynamic Braking Resistor
(DBR), use thermal protection and an input contactor that
will open the input 3-phase power circuit to the ASD in the event that a DBR over-temperature
condition occurs. In the event of a power source over-voltage condition or an ASD failure, the input
contactor will prevent hazardous DBR temperatures.
Dynamic Braking Resistors
shall be connected across terminals
PA
and
PB ONLY
(when used).
Connecting a
Dynamic Braking Resistor
elsewhere may cause a fire.
Heavy duty DBRs shall be wired using the same gauge wire as the motor leads. Light duty DBRs may
use one wire size smaller (AWG) than the motor leads.
The total wire length from the ASD to the DBR shall not exceed ten feet.
Because the heat generated by the DBR will affect the cooling capacity of the heat sink, the resistor
pack shall be mounted above or to the side of the ASD —
Never below the ASD
. Maintain a minimum
of six inches between the resistor pack and the ASD unit.
Note:
Dynamic braking is not available on the 100 HP – 400 HP GX9 ASDs.
If EMI/RFI noise is of concern, the DBR wiring shall be three-core screened cable. The screen shall
connect to the ASD enclosure and the resistor enclosure.
Содержание GX9 ASD
Страница 1: ...GX9 ASD Quick Start Guide TOSHIBA GX9 ASD Quick Start Guide DN 66900 001 March 2014 ...
Страница 2: ......
Страница 3: ...Document Number 66900 001 March 2014 GX9 ASD Quick Start Guide ...
Страница 4: ......
Страница 88: ...78 GX9 ASD Quick Start Guide Figure 33 GX9 ASD 5 0 20 HP Enclosure ...
Страница 89: ...GX9 ASD Quick Start Guide 79 Figure 34 GX9 ASD 25 75 HP Enclosure ...
Страница 90: ...80 GX9 ASD Quick Start Guide Figure 35 GX9 ASD 100 200 HP Enclosure ...
Страница 91: ...GX9 ASD Quick Start Guide 81 Figure 36 GX9 ASD 250 400 HP Enclosure ...
Страница 92: ...82 GX9 ASD Quick Start Guide Figure 37 GX9 ASD 500 800 HP Enclosure ...
Страница 93: ...GX9 ASD Quick Start Guide 83 Figure 38 GX9 ASD 900 1200 HP Enclosure ...
Страница 99: ......