Speed Band Output
Introduction
A G3’s output contacts can be programmed to change state based upon its output frequency. In the following
example, the customer’s system will see a short when the output frequency is between 40 and 50 Hz and an
open when at any other speed.
Connections
TERMINAL STRIP
ST CC
LOW A LOW C RCH A RCH B
To customer To customer
This works in either panel or remote mode. In remote, remember to include a direction reference
.
Programming
Group
Parameter
Value
UTILITY PARAMETERS
Blind Function Selection
1
UTILITY PARAMETERS
Terminal Selection Params Blind
1
TERMINAL SELECTION PARAMETERS
“Low” Contacts Function
4
TERMINAL SELECTION PARAMETERS
Low Speed Signal Output Freq
*40
TERMINAL SELECTION PARAMETERS
“Rch” Contacts Function
9
TERMINAL SELECTION PARAMETERS
Speed Reach Maximum Frequency
*50
TERMINAL SELECTION PARAMETERS
Speed Reach Minimum Frequency
*50
* change to adjust frequency band