19
Half Speed Command
Introduction
This application shows a way to make a G3 run at half of its current output frequency (whatever it may be)
upon closure of a contact. This guideline utilizes Override Control to accomplish the desired control.
Connections
TERMINAL STRIP
ST CC
PP RX
SWITCH 1 is located to the right of the phone jack on the control board under the keypad. Make sure it is set to the ‘10’ position. The
‘I’/’V’ switch does not apply to this guideline
.
Programming
Group
Parameter
New Value
UTILITY PARAMETERS
Blind Function Selection
1
UTILITY PARAMETERS
Feedback Parameters Blind
1
FEEDBACK PARAMETERS
Override Control Selection
7
FEEDBACK PARAMETERS
Override Multiplier Input Selection
3
FEEDBACK PARAMETERS
Override Change Multiplier
-50
This works in either panel or remote mode (connect direction reference as usual if in remote mode).
Change Override Change Multiplier to double, quarter, etc. your reference.