For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-
2192
49
Programming
Group
Parameter
Value
UTILITY PARAMETERS
Blind Function Selection
1
UTILITY PARAMETERS
Feedback Parameters Blind
1
UTILITY PARAMETERS
Frequency Setting Parameters Blind
1
FUNDAMENTAL PARAMETERS
Maximum Output Frequency
60
FUNDAMENTAL PARAMETERS
Acceleration Time #1
5
FUNDAMENTAL PARAMETERS
Deceleration Time #2
5
FUNDAMENTAL PARAMETERS
Upper Limit Frequency
60
FREQUENCY SETTING PARAMETERS
IV Terminal Standard or Adjustable
1
FREQUENCY SETTING PARAMETERS
IV Ref Point #2 Frequency
60
FEEDBACK PARAMETERS
Feedback Control Selection
1
FEEDBACK PARAMETERS
Feedback Input Signal Selection
2
FEEDBACK PARAMETERS
Proportional Gain
1.0
FEEDBACK PARAMETERS
Integral Gain
2.0
FEEDBACK PARAMETERS
Anti-Hunting Gain
0.0
The above programming assumes a system in which an increase in 4-20 mA feedback signal causes the
drive to reduce output frequency. If the system is such that increasing feedback should cause an increase
in output frequency, the bias/gain of the ‘IV’ terminal should be reversed by programming the following:
Group
Parameter
Value
UTILITY PARAMETERS
Blind Function Selection
1
UTILITY PARAMETERS
Feedback Parameters Blind
1
FREQUENCY SETTING PARAMETERS
IV Terminal Standard or Adjustable
1
FREQUENCY SETTING PARAMETERS
IV Reference Setting Point #1
20
FREQUENCY SETTING PARAMETERS
IV Ref Point #1 Frequency
60
FREQUENCY SETTING PARAMETERS
IV Reference Setting Point #2
100
FREQUENCY SETTING PARAMETERS
IV Ref Point #2 Frequency
0
Setting the Setpoint
In general, the setpoint is set by adjusting the setpoint to whatever level (frequency) is necessary to yield
the desired process variable setting. The commanded frequency and actual output frequency will most
likely not be the same; it is only the process variable’s (pressure, temperature, etc.) value that is of
concern. It is the ratio of Frequency Command to Maximum Output Frequency that the drive uses to
determine the feedback value it is trying to maintain (the setpoint).
Setpoint via keypad: Press LOCAL/REMOTE button to illuminate the panel’s green LED. Hit
RUN and adjust the Frequency Command to whatever value it takes to develop the desired process
variable value.