For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-
2192
60
Programming
Group
Parameter
New Value
UTILITY PARAMETERS
Blind Function Selection
1
UTILITY PARAMETERS
Terminal Selection Parameters Blind
1
UTILITY PARAMETERS
Frequency Setting Parameters Blind
1
UTILITY PARAMETERS
Feedback Parameters Blind
1
FUNDAMENTAL PARAMETERS #1
Maximum Output Frequency
60
FUNDAMENTAL PARAMETERS #1
Reverse Operation Disable Select
1
TERMINAL SELECTION PARAMETERS
Input Terminal Selection
1
TERMINAL SELECTION PARAMETERS
“S1” Input Terminal Function
13
FREQUENCY SETTING PARAMETERS
RX Terminal Standard or Adjustable
1
FREQUENCY SETTING PARAMETERS
RX Reference Setting Point #1
(2)
FREQUENCY SETTING PARAMETERS
RX Reference Point #1 Frequency
0
FREQUENCY SETTING PARAMETERS
RX Reference Setting Point #2
100
FREQUENCY SETTING PARAMETERS
RX Reference Point #2 Frequency
60
FEEDBACK PARAMETERS
Feedback Control Selection
1
FEEDBACK PARAMETERS
Feedback Input Signal Selection
3
FEEDBACK PARAMETERS
Proportional Gain
0.8
(1)
FEEDBACK PARAMETERS
Integral Gain
0.5
(1)
FEEDBACK PARAMETERS
Lag Time Constant
0.0
(1)
(1)
These are suggestions and will have to be field-adjusted. See Application Guideline 24 for PID
information.
(2)
The following is an example of how to adjust the RX Bias/Gain:
Suppose dancer output is 1-5 volts. Set the micro switch next to the phone jack on the control board in the
‘5” position. Suppose that the dancer output voltage when the dancer is in the desired position is 2.5
volts. 2.5/5.0 = 0.50 or 50 percent. Enter 50 into RX Reference Setting Point #1 (FREQUENCY
SETTING PARAMETERS group). After the following Super
User programming is done, the drive
will automatically adjust its output frequency to maintain the dancer’s output voltage
(and therefore
position) at 2.5 volts.
With the RX Bias/Gain programmed as above, the drive will increase its output frequency when
the dancer voltage is above 2.5 volts; it will decrease its output frequency whenever the dancer voltage
is below 2.5 volts. If this relationship is the opposite of what is desired for a particular dancer, program
RX Reference Point #2 Frequency (FREQUENCY SETTING
PARAMETERS group) to ‘-60’. Now
the drive will increase its output frequency whenever the dancer voltage is below 2.5
volts and
decrease its output frequency whenever the dancer voltage is above 2.5 volts.
Содержание G3