E6581741
- 10 -
EtherNet/IP parameters
Title
Communi
cation No.
Function Description
Factory
setting
c536
C536 EtherNet
Error
Monitor of the EtherNet error.
0: No error/clear error
1: Modbus TCP IO Scanning timeout
2: Network overload
3: Loss of Ethernet carrier
-
c554
C554
Web service (*3)
Enables web server.
0: Disable
1: Enable
1
c555
C555 Drive
Status
Monitor the inverter status.
3: Gate Block
4: Run
23: Fault
-
Modbus TCP parameters
Title
Communi
cation No.
Function Description
Factory
setting
c600-
c603
C600-
C603
IP Master (*3)
The IP address for PLC(Master) of the Modbus TCP.
0.0.0.0
c604
C604
IO Scan active (*3)
Enables IO Scan function.
0: Non-active
1: Active
0
(*3): This parameter is effective by reset. Please reset (power supply reset or
f899
=
1
) after changing a set point.
Warning
Mandatory
action
Set up “Communication error trip function (
c100
to
c103
and
c523
)” to stop the
inverter when EtherNet/IP™ - Modbus® TCP communication is deactivated.
When the parameters are changed, please reset
(power supply reset or
f899
=
1
)
the
inverter for the changes to take effect.
Содержание EtherNet/IP Modbus IPE002Z
Страница 57: ...E6581741 56 Select the Module as below Select revision of drive Put in Name and IP address and press OK button ...
Страница 61: ...E6581741 60 Select the Download Once again select the Download ...
Страница 64: ...E6581741 63 ...
Страница 83: ...E6581741 82 13 3 Drive monitor Main menu Monitoring The state of the drive can be confirmed on this page ...
Страница 85: ...E6581741 84 Input the write value to popup window ...
Страница 89: ...E6581741 88 13 9 TCP IP statistics Main menu Diagnostics You can check TCP IP status on this page 88E ...