E6581741
- 53 -
■
Examples of Instance 105/155
Access the inverter parameter is enabled using byte 1 to 5 of this Instance.
Set the communication number of the parameter to byte 2, 3 (Index), and the value to byte 4, 5 (Data).
c
Read the parameter
cmod
(Command mode selection, communication number is 0003).
Instance
Byte 15 14 13 12 11 10 9
8
7
6
5
4
3 2 1 0
Hex.
1, 0
0
0
0
0
0
0 0 0 0
0
0
0
0
0
0
0
0x0000
3, 2
0
0
0
0
0
0 0 0 0
0
0
0
0
0
1 1
0x0003
Output Instance 105
5, 4
-
-
-
-
-
-
- -
-
-
-
-
-
-
-
-
-
1, 0
0
0
0
0
0
0 0 0 0
0
0
0
0
0
0
0
0x0000
3, 2
0
0
0
0
0
0 0 0 0
0
0
0
0
0
1 1
0x0003
Input Instance 155
(
cmod
is 0.)
5, 4
0
0
0
0
0
0 0 0 0
0
0
0
0
0
0
0
0x0000
d
Read the parameter
f268
(Initial value of UP/DOWN frequency).
Instance
Byte 15 14 13 12 11 10 9
8
7
6
5
4
3 2 1 0
Hex.
1, 0
0
0
0
0
0
0 0 0 0 0
0
0
0
0
0
0
0x0000
3, 2
0
0
0
0
0
0
1
0 0
1
1
0
1
0 0 0 0x0268
Output Instance 105
5, 4
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1, 0
0
0
0
0
0
0 0 0 0 0
0
0
0
0
0
0
0x0000
3, 2
0
0
0
0
0
0
1
0 0
1
1
0
1
0 0 0 0x0268
Input Instance 155
(
f268
is 60.0Hz.)
5,
4 0 0 0
1
0
1
1
1
0
1
1
1
0 0 0 0 0x1770
3
Write “60 (Hz)” to the parameter
sr1
(Preset speed 1, communication number is 0018).
Instance
Byte 15 14 13 12 11 10 9
8
7
6
5
4
3 2 1 0
Hex.
1, 0
1
0
0
0
0
0 0 0 0 0
0
0
0
0
0
0
0x8000
3, 2
0
0
0
0
0
0 0 0 0 0
0
1
1
0 0 0 0x0018
Output Instance 105
5,
4 0 0 0
1
0
1
1
1
0
1
1
1
0 0 0 0 0x1770
1, 0
0
0
0
0
0
0 0 0 0 0
0
0
0
0
0
0
0x0000
3, 2
0
0
0
0
0
0 0 0 0 0
0
1
1
0 0 0 0x0018
Input Instance 155
(OK)
5,
4 0 0 0
1
0
1
1
1
0
1
1
1
0 0 0 0 0x1770
1, 0
0
1
0
0
0
0 0 0 0 0
0
0
0
0
0
0
0x4000
3, 2
0
0
0
0
0
0 0 0 0 0
0
1
1
0 0 0 0x0018
Input Instance 155
(NG)
(Error code *)
5, 4
0
0
0
0
0
0 0 0 0 0
0
0
0
0
0
1
0x0001
*Data of "Error code"
0x0001: Error
Содержание EtherNet/IP Modbus IPE002Z
Страница 57: ...E6581741 56 Select the Module as below Select revision of drive Put in Name and IP address and press OK button ...
Страница 61: ...E6581741 60 Select the Download Once again select the Download ...
Страница 64: ...E6581741 63 ...
Страница 83: ...E6581741 82 13 3 Drive monitor Main menu Monitoring The state of the drive can be confirmed on this page ...
Страница 85: ...E6581741 84 Input the write value to popup window ...
Страница 89: ...E6581741 88 13 9 TCP IP statistics Main menu Diagnostics You can check TCP IP status on this page 88E ...