E6581741
- 1 -
-
1
-
Introduction
Thank you for purchasing the “EtherNet/IP™ - Modbus
®
TCP option (IPE002Z)” for
TOSVERT VF-MB1/S15 inverter. Before using EtherNet/IP™ - Modbus
®
TCP module,
carefully read this function manual in order to completely and correctly utilize its excellent
performance.
This option needs the option adaptor to connect VF-S15 which type form is SBP009Z.
Please match here and buy it when SBP009Z is not at hand yet.
After reading this function manual, please keep it handy for future reference.
For details of its general handling, see an instruction manual attached with the option
unit.
- TOSVERT VF-MB1 Instruction Manual ························································· E6581697
- TOSVERT VF-S15 Instruction Manual ·························································· E6581611
- TOSVERT VF-MB1/S15 communication option Precautions Manual··········· E6581739
- TOSVERT VF-MB1 Communication Function Instruction Manual ················ E6581726
- TOSVERT VF-S15 Communication Function Instruction Manual ················· E6581913
EtherNet/IP™ is a trademark of ControlNet International, Ltd.
Modbus
®
TCP is a registered trademark of AEG Schneider Automation International S.A.S.
Handling in general
Warning
Prohibited
Do not connect or disconnect a network cable while the Inverter power is on.
It may lead to electric shocks or fire.
Mandatory
See the instruction manual attached with the option unit for cautions the handling.
Otherwise, it may lead to electric shocks, fire, injuries or damage to product.
Network control
Warning
Prohibited
Do not send the value out of the valid range to objects and attributes.
Otherwise, the motor may suddenly start/stop and that may result in injuries.
Mandatory
Use an additional safety device with your system to prevent a serious accident due to the
network malfunctions. Usage without an additional safety device may cause an accident.
Caution
Mandatory
Set up “Communication error trip function (see below)” to stop the Inverter when the
option unit is deactivated by an unusual event such as tripping, an operating error,
power outage, failure, etc.
- Network Time-Out, Inverter operation at disconnection, Preset speed operation
selection
(Refer to "
3.2.3 Network error detection (c100 -
c103,
c523)
" for details)
Deactivated the option module may cause an accident, if the “Communication error trip
function” is not properly set up.
Make sure that the operation signals are STOP before resetting Inverter’s fault. The
motor may suddenly start and that may result in injuries.
Notes on operation
Notes
When the control power is shut off by the instantaneous power failure, communication
will be unavailable for a while.
The Life of EEPROM is approximately 100,000 times. Avoid writing a command more
than 100,000 times to the same parameter of the Inverter and the option module.
Содержание EtherNet/IP Modbus IPE002Z
Страница 57: ...E6581741 56 Select the Module as below Select revision of drive Put in Name and IP address and press OK button ...
Страница 61: ...E6581741 60 Select the Download Once again select the Download ...
Страница 64: ...E6581741 63 ...
Страница 83: ...E6581741 82 13 3 Drive monitor Main menu Monitoring The state of the drive can be confirmed on this page ...
Страница 85: ...E6581741 84 Input the write value to popup window ...
Страница 89: ...E6581741 88 13 9 TCP IP statistics Main menu Diagnostics You can check TCP IP status on this page 88E ...