E6581741
- 18 -
3.2.4.7.
fd01
(Inverter operating status 1)
bit Function
0
1
Note
0
Failure FL
No output
Under in
progress
-
1 Failure
Not
tripped
Tripped
Trip status includes
rtry
and
the trip retention status are also
regarded as tripped statuses.
2
Alarm
No alarm
Alarm issued
-
3
Under voltage (
moff
) Normal Under
voltage
-
4
Motor selection (1 or 2)
(THR 2 selection)
Motor 1 (THR1)
Motor 2 (THR2)
THR1:
pt
= setting value,
vl
,
vlv
,
vb
,
thr
THR2:
pt
= 0,
f170
,
f171
,
f172
,
f173
5
PID control off
PID control
permitted
PID control
prohibits
-
6
Acceleration/deceleratio
n pattern selection (1 or
2)
Acceleration/dec
eleration pattern
1 (AD1)
Acceleration/dec
eleration pattern
2 (AD2)
AD1:
acc
,
dec
AD2:
f500
,
f501
7 DC
braking
OFF
Forced DC
braking
-
8
Jog run
OFF
Jog run
-
9
Forward / reverse run
Forward run
Reverse run
-
10 Run/stop
Stop
Run
-
11
Coast stop (ST = OFF)
ST=ON
ST=OFF
-
12 Emergency
stop
No emergency
stop status
Emergency
stop status
-
13
Standby ST=ON
Start-up process
Standby
Standby: Initialization
completed, not failure stop
status, not alarm stop status
(
moff
,
ll
forced stop),
ST=ON, and RUN=ON
14 Standby
Start-up
process
Standby
Standby: Initialization completed,
not failure stop status and not
alarm stop status (
moff
,
ll
forced stop)
15 (Reserved)
Undefined
-
Note: Don’t use the reserved bit for the judgment.
3.2.4.8.
fd00
(Output frequency)
The current output frequency is read into 0.01Hz of units and by the hexadecimal number.
For example, when the output frequency is 80Hz, 0x1F40 (hexadecimal number) are read.
Since the minimum unit is 0.01%,
0x1F40 (Hex.) = 8000(Dec.) * 0.01 = 80 (Hz)
Also about the following parameters, these are the same as this.
-
fd22
(Feedback value of PID)............................................... Unit: 0.01Hz
-
fd16
(Estimated speed) ........................................................ Unit: 0.01Hz
-
fd29
(Input power) ................................................................ Unit: 0.01kW
-
fd30
(Output power) ............................................................. Unit: 0.01kW
Содержание EtherNet/IP Modbus IPE002Z
Страница 57: ...E6581741 56 Select the Module as below Select revision of drive Put in Name and IP address and press OK button ...
Страница 61: ...E6581741 60 Select the Download Once again select the Download ...
Страница 64: ...E6581741 63 ...
Страница 83: ...E6581741 82 13 3 Drive monitor Main menu Monitoring The state of the drive can be confirmed on this page ...
Страница 85: ...E6581741 84 Input the write value to popup window ...
Страница 89: ...E6581741 88 13 9 TCP IP statistics Main menu Diagnostics You can check TCP IP status on this page 88E ...