E6581741
- 72 -
9. IO Scanning service
9.1. Presentation
The IO Scanning service is used to exchange I/O data between:
A controller or PLC (IO Scanner).
Devices (IO Scanning servers).
This exchange is usually performed by implicit services, thus avoiding the need to
program the controller (PLC).
The IO Scanner periodically generates the Read/Write Multiple Registers (23 = 0x17)
request.
The IO Scanning service operates if it has been enabled in the PLC and the drive.
The drive parameters assigned to IO Scanning have been selected by default. This
assignment can be modified by configuration.
The drive IO Scanning service can also be configured by the option Modbus server.
When the IO Scanning service has been enabled in the VF-MB1/S15 drive:
A TCP connection is assigned to it.
The parameters assigned in the periodic variables are exchanged cyclically between the
option and the drive.
The parameters assigned in the periodic output variables are reserved for IO Scanning.
They cannot be written by another Modbus service, even if the IO Scanner is not sending
its periodic output variables.
9.2. Periodic
variables
Word No.
Output variables (written by IO Scanner)
Input variables (read by IO Scanner)
0 Reserved
Reserved
1
Scanner write word 1 – configurable (
c001
) Scanner read word 1 – configurable (
c021
)
2
Scanner write word 2 – configurable (
c002
) Scanner read word 2 – configurable (
c022
)
3
Scanner write word 3 – configurable (
c003
) Scanner read word 3 – configurable (
c023
)
4
Scanner write word 4 – configurable (
c004
) Scanner read word 4 – configurable (
c024
)
5
Scanner write word 5 – configurable (
c005
) Scanner read word 5 – configurable (
c025
)
6
Scanner write word 6 – configurable (
c006
) Scanner read word 6 – configurable (
c026
)
7-31 Reserved
Reserved
It is possible to configure the assignment of periodic variables 1 to 6.
Please refer to "parameter" about configurable.
Содержание EtherNet/IP Modbus IPE002Z
Страница 57: ...E6581741 56 Select the Module as below Select revision of drive Put in Name and IP address and press OK button ...
Страница 61: ...E6581741 60 Select the Download Once again select the Download ...
Страница 64: ...E6581741 63 ...
Страница 83: ...E6581741 82 13 3 Drive monitor Main menu Monitoring The state of the drive can be confirmed on this page ...
Страница 85: ...E6581741 84 Input the write value to popup window ...
Страница 89: ...E6581741 88 13 9 TCP IP statistics Main menu Diagnostics You can check TCP IP status on this page 88E ...