E6581741
- 76 -
10.4. Configuring periodic variables
This window is used to configure the IO Scanning function, described in the IO Scanning
Service section on page 72.
Example:
•The periodic variables of the drive at IP address 192.168.1.12 are associated with PLC
data words.
•The drive periodic output variables (control) are associated with the 32 words (WR
count) starting at PLC address %MW550 (Write Ref.).
•The drive periodic input variables (monitoring) are associated with the 32 words (RD
count) starting at PLC address %MW500 (Read Ref.).
The addresses for the PLC %MW words correspond to the configuration in the previous example.
PLC
address
Periodic output variable
(default assignment)
Configurable
%MW 550
Reserved
No
%MW 551
Scanner write word 1
Yes (
c001
)
%MW 552
Scanner write word 2
Yes (
c002
)
%MW 553
Scanner write word 3
Yes (
c003
)
%MW 554
Scanner write word 4
Yes (
c004
)
%MW 555
Scanner write word 5
Yes (
c005
)
%MW 556
Scanner write word 6
Yes (
c006
)
%MW 557
to
%MW 581
Reserved No
PLC
address
Periodic output variable
(default assignment)
Configurable
%MW 500
Reserved
No
%MW 501
Scanner read word 1
Yes (
c021
)
%MW 502
Scanner read word 2
Yes (
c022
)
%MW 503
Scanner read word 3
Yes (
c023
)
%MW 504
Scanner read word 4
Yes (
c024
)
%MW 505
Scanner read word 5
Yes (
c025
)
%MW 506
Scanner read word 6
Yes (
c026
)
%MW 507
to
%MW 531
Reserved No
Содержание EtherNet/IP Modbus IPE002Z
Страница 57: ...E6581741 56 Select the Module as below Select revision of drive Put in Name and IP address and press OK button ...
Страница 61: ...E6581741 60 Select the Download Once again select the Download ...
Страница 64: ...E6581741 63 ...
Страница 83: ...E6581741 82 13 3 Drive monitor Main menu Monitoring The state of the drive can be confirmed on this page ...
Страница 85: ...E6581741 84 Input the write value to popup window ...
Страница 89: ...E6581741 88 13 9 TCP IP statistics Main menu Diagnostics You can check TCP IP status on this page 88E ...