E6581741
- 69 -
8.8. "43 (0x2B) Read Device identification" function
The "Read/Write Multiple Registers" service is reserved for setting up the IO Scanning
service (see "IO Scanning section").
Example in VF-MB1 is shown below.
Request format:
Byte Meaning
0
Function Code =
2Bh
2Bh
1
Type of MEI
0Eh
2
Read Device ID code
01: Basic
02: Regular
03: Extended
3 Object
ID
0
Response format: (ID = 248)
Byte
Meaning
With the IPE002Z
0
Function Code =
2Bh
2Bh
1
Type of MEI
0Eh
2
Read Device ID code
01: Basic
02: Regular
03: Extended
3 Conformity
Level
2
4 More
Follows
0
5
Next Object Id
0
6
Number Of Objects
3 for Basic.
6 for Regular or Extended
7
Obj 0 Id
Æ
Vendor Name
0
8
Obj 0 length
7
9-15
Obj 0 value
“TOSHIBA”
16
Obj 1 Id
Æ
ProductCode
1
17
Obj 1 length
13
18-30
Obj 1 value
“VFMB1S-2007PL”
31
Obj 2 Id
Æ
Version
2
32
Obj 2 length
5
33-37
Obj 2 value
“10801”
38
Obj 4 Id
Æ
Product Name
4
39
Obj 4 length
6
40-45
Obj 4 value
“VF-MB1”
46
Obj 5 Id
Æ
Model Name
5
47
Obj 5 length
3
44-58
Obj 5 value
“TSB”
59 Obj 6 Id
Æ
UserApplicationName
6
60
Obj 6 length
16 maximum
61-80
Obj 6 value
“ModbusTCP”
Only for
Regular
and
Extended
Содержание EtherNet/IP Modbus IPE002Z
Страница 57: ...E6581741 56 Select the Module as below Select revision of drive Put in Name and IP address and press OK button ...
Страница 61: ...E6581741 60 Select the Download Once again select the Download ...
Страница 64: ...E6581741 63 ...
Страница 83: ...E6581741 82 13 3 Drive monitor Main menu Monitoring The state of the drive can be confirmed on this page ...
Страница 85: ...E6581741 84 Input the write value to popup window ...
Страница 89: ...E6581741 88 13 9 TCP IP statistics Main menu Diagnostics You can check TCP IP status on this page 88E ...